Frost thermostat STT900 5127040000

  • Model: 010.004.110
Frost thermostat STT900 5127040000
Manufacturer: Schneider Electric
The frost protection thermostats are used for air, or water-side temperature monitoring of heat exchangers, hot water circulation systems, water/air heaters, e.g. in ventilation and air conditioning systems and to avoid frost damage. The product features a small operating differential and high reproducibility. Resetting of the STT900 occurs automatically.
The output would typically switch off ventilators, close outside air flaps, open up air heating valves, switch on air heat pumps, switch off  refrigeration compressors, switch off  air humidifiers, or initiate a visual and/or acoustic frost alarm.
Location of  these items is not critical, even in harsh environments as they are all rated to IP65.

Main characteristics

Switching capacity10 (2) A, 250Vac
gold-plated switching contacts allow signal voltage switching < 24 V
Setting range-10 °C ...+ 15 °C / 14 °F... 59 °F
factory setting to w = 5 °C (41 °F)
Operating difference2 ± 1 K (3.6 ± 1.8 °F)
Reproducibility± 0.5 K (± 0.9 °F)
Contactdustproof micro switch as single-pole potential-free changeover contact.
Sensor responding length: ca. 40 cm
Length of capillary tube0.6 m (2 ft.)
Resettingautomatic
Permissible mediumair
Ambient temperatures:maximum operating temperature: 70 °C (158 °F)
minimum operating temperature: + min. 2 °C (min. 3.6 °F)
Storage / transport- 30 ...+ 70 °C (- 22 ...+ 158 °F)
Process connectionby mounting clamps (included in the scope of delivery)
Connecting headplastic, material polyamide, 30 % glass-globe-reinforced, color pure white (similar RAL 9010)
Размеры120 х 80 х 50 mm
Other materials:
Mechanical sheet metal parts
Capillary tube
Capillary tube filling
Switching contacts

galvanized steel
copper
R 507
Ag / Ni (90% / 10%) gold-plated (3μm)
Electrical connection0.14 - 2.5 mm²
Cable unionM 20 x 1.5, including strain relie
Protection classI (according to EN 60 730-1)
IP 65 (according to EN 60 529)
StandardsCE conformity, EMC directive 89 / 336 / EWG, Low-voltage directive 73 / 23 / EWG
Output Contact Function1 - 4 danger of frost / sensor breakage
1 - 2 normal operation

Frost thermostats series STT

Model number Part number Capillary length Reset type Permissible medium
STT900 5127040000 0.6 m (2 ft.) Automatic Air
STT901 5127010000 1.8 m (5.9 ft.) Automatic Water
STT902 5127020000 3 m (9.8 ft.) Automatic Air
STT903 5127000000 6 m (19.7 ft.) Automatic Air
STT904 5127030000 12 m (39 ft.) Automatic Air
STT910 5127090000 0.6 m (2 ft.) Manual Air
STT911 5127060000 1.8 m (5.9 ft.) Manual Water
STT912 5127070000 3 m (9.8 ft.) Manual Air
STT913 5127050000 6 m (19.7 ft.) Manual Air
STT914 5127080000 12 m (39 ft.) Manual Air
Questions
WhatsAppTelegramViberVKemail