General characteristics |
---|
Number of poles | 1 |
Number of connections | 4 |
Nominal cross-section | 10 mm² |
Colour | blue |
Insulating material | PA |
Flammability rating according to UL 94 | V2 |
Rated surge voltage | 8 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Max power dissipation for nominal condition | 1,82 W |
Max load current | 76 A (with 16 mm² conductor cross section) |
Nominal current IN | 57 A |
Nominal voltage UN | 1000 V |
Connection data |
---|
Connection method | screw connection |
Screw dimension | M4 |
Stripping length | 10 mm |
Min tightening torque | 1,5 N·m |
Max tightening torque | 1,8 N·m |
Solid conductor cross-section (min) | 0,5 mm² |
Solid conductor cross-section (max) | 16 mm² |
Solid conductor cross-section AWG (min) | 20 |
Solid conductor cross-section AWG (max) | 6 |
Flexible conductor cross-section (min) | 0,5 mm² |
Flexible conductor cross-section (max) | 10 mm² |
Flexible conductor cross-section AWG (min) | 20 |
Flexible conductor cross-section AWG (max) | 8 |
Flexible conductor cross section, with ferrule without plastic sleeve (min) | 0,5 mm² |
Flexible conductor cross section, with ferrule without plastic sleeve (max) | 10 mm² |
Flexible conductor cross section, with ferrule and plastic sleeve (min) | 0,5 mm² |
Flexible conductor cross section, with ferrule and plastic sleeve (max) | 6 mm² |
Two solid cables with the same cross-section (min) | 0,5 mm² |
Two solid cables with the same cross-section (max) | 4 mm² |
Two stranded conductors with the same cross-section (min) | 0,5 mm² |
Two stranded conductors with the same cross-section (max) | 4 mm² |
2 conductors with the same cross section, stranded, TWIN ferrules with plastic sleeve (min) | 0,5 mm² |
2 conductors with the same cross section, stranded, TWIN ferrules with plastic sleeve (max) | 6 мм² |
2 conductors with the same cross section, stranded, ferrules without plastic sleeve (min) | 0,5 mm² |
2 conductors with the same cross section, stranded, ferrules without plastic sleeve (max) | 2,5 mm² |