Green flush pushbutton XB7EA31P

  • Model: 003.105.100
Green flush pushbutton XB7EA31P
Manufacturer: Schneider Electric
Green flush pushbutton XB7EA31P with spring return.
Contacts configuration 1NO.
Rated operating current 0.3A at 240VAC (AC-14).
Mounting diameter 22mm.
Contact operation - slow break.
Degree of protection IP54 (front face).

Main

range of productHarmony XB7
product or component typePush-button
device short nameXB7
mounting diameter22 mm
sale per indivisible quantity10
IP degree of protectionIP20 (rear face) conforming to IEC 60529
IP54 (front face) conforming to IEC 60529
shape of signaling unit headRound
type of operatorspring return
operator profileGreen flush, unmarked
contacts type and composition1 NO
connections - terminalsScrew clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, 1 x 0.34...2 x 2.5 mm² without cable end conforming to EN/IEC 60947-1
device presentationMonolithic product

Complementary

CAD overall width29 mm
CAD overall height29 mm
CAD overall depth52 mm
terminals description ISO n°1(13-14)NO
net weight0.02 kg
device mountingFixing hole - diameter: 22.5 mm 22.3 +0.4/0 conforming to EN/IEC 60947-1
fixing center>= 30 x 40 mm (support panel) metal - thickness: 1…6 mm
>= 30 x 40 mm (support panel) plastic - thickness: 2…6 mm
fixing modeFixing nut beneath head: 2…2.4 N.m
contact operationSlow-break
positive openingWithout
mechanical durability1000000 cycles
tightening torque0.8…1.2 N.m conforming to EN 60947-1
shape of screw headCross compatible with JIS No 1 screwdriver
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
short-circuit protection4 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage250 V (pollution degree 3) conforming to EN/IEC 60947-1
[Uimp] rated impulse withstand voltage4 kV conforming to EN/IEC 60947-1
[Ie] rated operational current0.1 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1
0.22 A at 125 V, DC-13, R300 conforming to EN/IEC 60947-5-1
0.3 A at 240 V, AC-14, D300 conforming to EN/IEC 60947-5-1
0.6 A at 120 V, AC-14, D300 conforming to EN/IEC 60947-5-1
electrical durability1000000 cycles, DC-13, 0.3 A at 24 V, operating rate <216000 cyc mn, load factor: 0.5 conforming to en iec 60947-5-1 appendix c
1000000 cycles, AC-15, 0.03 A at 230 V, operating rate <216000 cyc mn, load factor: 0.5 conforming to en iec 60947-5-1 appendix c
1000000 cycles, AC-15, 0.09 A at 240 V, operating rate <108000 cyc mn, load factor: 0.5 conforming to en iec 60947-5-1 appendix c< td>
electrical reliabilityΛ <= 10exp(-6) at 17 V, 5 mA conforming to EN/IEC 60947-5-4

Environment

protective treatmentTH
ambient air temperature for storage-40…70 °C
ambient air temperature for operation-25…70 °C
overvoltage categoryClass II conforming to IEC 60536
NEMA degree of protectionNEMA 12
standardsEN/IEC 60947-1
CSA C22.2 No 14
JIS C8201-5-1
UL 508
EN/IEC 60947-5-1
JIS C8201-1
vibration resistance5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6
shock resistance50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27