Solid state relay 77.01.8.230.8051

  • Model: 005.066.142
Solid state relay 77.01.8.230.8051
Manufacturer: Finder (Italy)
Modular solid state relay 77.01.8.230.8051 is used for finer control requiring short operate time (specially motor control), 3-phase general purpose, and also where AC input phase is different from AC output phase.
• 1 normally open contact (1NO) for 5A;
• Random switch-on;
• 35mm DIN rail mount.
$50.62
 pcs

Characteristics

Output specification
Output configuration1 NO (SPST-NO)
Rated current In/ Max peak current (10ms)5А/300А
Rated voltage230V АС
Rated voltage range(60...240)V АС
Switching voltage range(48...265)V АС
Repetitive peak off-state voltage800V
Rated load АС7а (cos φ= 0.8)5A
Rated load АС15
Single phase motor rating (230V АС)0.37kW
230V lamps ratingincandescent/halogen - 800W
compact fluorescent (CFL)/led - 400W
electronic ballast fluorescent tubes - 800W
electromagnetic ballast compensated fluorescent tubes - 250W
Min switching current at 230V AC100 mA
Typical off-state leakage current at 230V mA1 mA
Max on-state voltage drop at t=25°C and 5А/100mА0,85V/1,5V
Power loss at 5А4W
Input specification
Nominal voltage Un230V AC
Rated powerАС (50 Hz) - 3.6VA
DC - 0.3W
Operating range(90...265)V AC
Must drop-out voltage, АС/DC24V
Technical data
Electrical life10·106 cycles
Operate/release time9/8 ms
Insulation between input and output (1,2/50 μs)5kV
Dielectric strength2500V АС
Ambient temperature-20°C...+70°C
Protection categoryIP20
Terminals
Screw torque0,8 N·m
Max solid cable size1x6/2x4 mm2
1x10/2x12 AWG
Max stranded cable size1х4/2х2,5 mm2
1х12/2х14 AWG
Wire strip length9 mm

Output specification

Output RMS current vs ambient temperature at 265V DC
Output RMS current vs ambient temperature for relay 77.01.8.230.8051
Inrush peak current vs inrush time
Inrush peak current vs inrush time for relay 77.01.8.230.8051

Dimensions and simplified circuit diagram

Dimensions and simplified circuit diagram of relays series 77.01