SR3B261FU Modular smart relay Zelio Logic

  • Model: 005.180.006
SR3B261FU Modular smart relay Zelio Logic
Manufacturer: Schneider Electric
Barcode: 3389110550009
Modular smart relay SR3B261FU Zelio Logic 100...240 VAC.
- Discrete inputs - 16 PCs, discrete input voltage-100...240 VAC.
- Relay outputs - 10 PCs. Output current- 5 A for 2 outputs, 8 A for 8 outputs.
Main
range of productZelio Logic
product or component typeModular smart relay
Complementary
local displayWith
number or control scheme lines0...500 with FBD programming
0...240 with ladder programming
cycle time6...90 ms
backup time10 years at 25 °C
clock drift6 s/month at 25 °C
12 min/year at 0...55 °C
checksProgram memory on each power up
[Us] rated supply voltage100...240 V AC
supply voltage limits85...264 V
supply frequency50/60 Hz
supply current100 mA at 100 V (without extension)
50 mA at 240 V (without extension)
60 mA at 240 V (with extensions)
80 mA at 100 V (with extensions)
power consumption in VA12 VA without extension
17 VA with extensions
isolation voltage1780 V
protection typeAgainst inversion of terminals (control instructions not executed)
discrete input number16
discrete input voltage100...240 V AC
discrete input current0.6 mA
discrete input frequency47...53 Hz
57...63 Hz
voltage state 1 guaranteed⩾79 V for discrete input
voltage state 0 guaranteed⩽ 40 V for discrete input
current state 1 guaranteed⩾ 0.17 mA for discrete input
current state 0 guaranteed⩽ 0.5 mA for discrete input
input impedance350 kOhm (discrete input)
number of outputs5 A for 2 outputs (relay output)
8 A for 8 outputs (relay output)
output voltage limits24...250 V AC (relay output)
5...30 V DC (relay output)
contacts type and compositionNO for relay output
output thermal current5 A for 2 outputs (relay output)
8 A for 8 outputs (relay output)
electrical durability500000 cycles AC-12 at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
500000 cycles AC-15 at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1
500000 cycles DC-12 at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
500000 cycles DC-13 at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1
switching capacity in mA⩾ 10 mA at 12 V (relay output)
operating rate in Hz0.1 Hz (at Ie) for relay output
10 Hz (no load) for relay output
mechanical durability10000000 cycles (relay output)
[Uimp] rated impulse withstand voltage4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
clockWithout
response time10 ms (from state 0 to state 1) for relay output
5 ms (from state 1 to state 0) for relay output
50 ms with ladder programming (from state 0 to state 1) for discrete input
50 ms with ladder programming (from state 1 to state 0) for discrete input
50...255 ms with FBD programming (from state 0 to state 1) for discrete input
50...255 ms with FBD programming (from state 1 to state 0) for discrete input
connections - terminalsScrew terminals, clamping capacity: 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14 semi-solid
Screw terminals, clamping capacity: 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14 solid
Screw terminals, clamping capacity: 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14 flexible with cable end
Screw terminals, clamping capacity: 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16 solid
Screw terminals, clamping capacity: 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18 flexible with cable end
tightening torque0.5 N.m
overvoltage categoryIII conforming to EN/IEC 60664-1
product weight0.4 kg
Environment
immunity to microbreaks⩽ 10 ms
product certificationsCSA
C-Tick
GL
GOST
UL
standardsEN/IEC 60068-2-27 Ea
EN/IEC 60068-2-6 Fc
EN/IEC 61000-4-11
EN/IEC 61000-4-12
EN/IEC 61000-4-2 level 3
EN/IEC 61000-4-3
EN/IEC 61000-4-4 level 3
EN/IEC 61000-4-5
EN/IEC 61000-4-6 level 3
IP degree of protectionIP20 (terminal block) conforming to IEC 60529
IP40 (front panel) conforming to IEC 60529
environmental characteristicEMC directive conforming to EN/IEC 61000-6-2
EMC directive conforming to EN/IEC 61000-6-3
EMC directive conforming to EN/IEC 61000-6-4
EMC directive conforming to EN/IEC 61131-2 zone B
Low voltage directive conforming to EN/IEC 61131-2
disturbance radiated/conductedClass B conforming to EN 55022-11 group 1
pollution degree2 conforming to EN/IEC 61131-2
ambient air temperature for operation-20...40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2
-20...55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
ambient air temperature for storage-40...70 °C
operating altitude2000 m
altitude transport⩽ 3048 m
relative humidity95 % without condensation or dripping water
Questions