SR3B261BD Modular smart relay Zelio Logic

  • Model: 005.180.007
  • photo 3
  • photo 4
SR3B261BD Modular smart relay Zelio Logic
Manufacturer: Schneider Electric
Modular smart relay SR3B261BD Zelio Logic 24 VDC.
- Discrete inputs - 16 PCs, discrete input voltage-24 VDC.
- Relay outputs - 10 PCs. Output current- 5 A for 2 outputs, 8 A for 8 outputs.
Main
range of productZelio Logic
product or component typeModular smart relay
Complementary
local displayWith
number or control scheme lines0…500 with FBD programming
0…240 with ladder programming
cycle time6…90 ms
backup time10 years at 25 °C
clock drift12 min/year at 0…55 °C
6 s/month at 25 °C
checksProgram memory on each power up
[Us] rated supply voltage24 V
supply voltage limits19.2…30 V
maximum supply current190 mA (without extension)
300 mA (with extensions)
power dissipation in W10 W with extensions
6 W without extension
reverse polarity protectionWith
discrete input number16 conforming to EN/IEC 61131-2 type 1
discrete input typeResistive
discrete input voltage24 V DC
discrete input current4 mA
counting frequency1 kHz for discrete input
voltage state 1 guaranteed>= 15 V for I1...IA and IH...IR discrete input circuit
>= 15 V for IB...IG used as discrete input circuit
voltage state 0 guaranteed≤ 5 V for I1...IA and IH...IR discrete input circuit
≤ 5 V for IB...IG used as discrete input circuit
current state 1 guaranteed>= 1.2 mA (IB...IG used as discrete input circuit)
>= 2.2 mA (I1...IA and IH...IR discrete input circuit)
current state 0 guaranteed≤ 0.5 mA (IB...IG used as discrete input circuit)
≤ 0.75 mA (I1...IA and IH...IR discrete input circuit)
input compatibility3-wire proximity sensors PNP for discrete input
analogue input number6
analogue input typeCommon mode
analogue input range0...10 V
0...24 V
maximum permissible voltage30 V for analogue input circuit
analogue input resolution8 bits
LSB value39 mV for analogue input circuit
conversion timeSmart relay cycle time for analogue input circuit
conversion error+/- 5 % at 25 °C for analogue input circuit
+/- 6.2 % at 55 °C for analogue input circuit
repeat accuracy+/- 2 % at 55 °C for analogue input circuit
operating distance10 m between stations, with screened cable (sensor not isolated) for analogue input circuit
input impedance12 kOhm for IB...IG used as analogue input circuit
12 kOhm for IB...IG used as discrete input circuit
7.4 kOhm for I1...IA and IH...IR discrete input circuit
number of outputs10 relay
output voltage limits24...250 V AC (relay output)
5...30 V DC (relay output)
contacts type and compositionNO for relay output
output thermal current5 A for 2 outputs for relay output
8 A for 8 outputs for relay output
electrical durabilityAC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1
DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1
switching capacity in mA>= 10 mA at 12 V (relay output)
operating rate in Hz0.1 Hz (at Ie) for relay output
10 Hz (no load) for relay output
mechanical durability10000000 cycles for relay output
[Uimp] rated impulse withstand voltage4 kV EN/IEC 60947-1 and EN/IEC 60664-1
clockWith
response time10 ms (from state 0 to state 1) for relay output
5 ms (from state 1 to state 0) for relay output
connections - terminalsScrew terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid
Screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid
Screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end
tightening torque0.5 N.m
overvoltage categoryIII conforming to EN/IEC 60664-1
net weight0.4 kg

Environment

immunity to microbreaks1 ms
product certificationsGL
C-Tick
CSA
UL
GOST
standardsEN/IEC 61000-4-2 level 3
EN/IEC 61000-4-5
EN/IEC 61000-4-6 level 3
EN/IEC 61000-4-11
EN/IEC 61000-4-3
EN/IEC 60068-2-27 Ea
EN/IEC 61000-4-12
EN/IEC 60068-2-6 Fc
EN/IEC 61000-4-4 level 3
IP degree of protectionIP20 (terminal block) conforming to IEC 60529
IP40 (front panel) conforming to IEC 60529
environmental characteristicEMC directive conforming to EN/IEC 61000-6-2
EMC directive conforming to EN/IEC 61000-6-3
EMC directive conforming to EN/IEC 61000-6-4
EMC directive conforming to EN/IEC 61131-2 zone B
Low voltage directive conforming to EN/IEC 61131-2
disturbance radiated/conductedClass B conforming to EN 55022-11 group 1
pollution degree2 conforming to EN/IEC 61131-2
ambient air temperature for operation-20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2
-20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
ambient air temperature for storage-40…70 °C
operating altitude2000 m
maximum altitude transport3048 m
relative humidity95 % without condensation or dripping water
Questions