Relay RSL1GB4ND

  • Model: 005.006.140
Relay RSL1GB4ND
Manufacturer: Schneider Electric
Barcode: 3606480078002
Harmony, Slim interface plug-in relay, 6 A, 1 CO, low level, coil 60 V DC

Main

range of productHarmony Electromechanical Relays
series nameSlim interface relay
product or component typePlug-in relay
device short nameRSL
contacts type and composition1 C/O
contact operationLow level
[Uc] control circuit voltage60 V DC
[Ithe] conventional enclosed thermal current6 A at -40…55 °C
status LEDWithout
control typeWithout push-button

Complementary

shape of pinFlat (PCB type)
average resistance16600 Ohm at 23 °C +/- 15 %
rated operational voltage limits45...84 V DC
[Ui] rated insulation voltage250 V conforming to EN/IEC
277 V conforming to cUL
[Uimp] rated impulse withstand voltageIEC 6 kV
contacts materialSilver alloy - gold plated (AgSnO2)
[Ie] rated operational current6 A (AC-1/DC-1) conforming to IEC/UL
minimum switching current1 mA
maximum switching voltage277 V
Minimum switching voltage24 V
maximum switching capacity1500 VA
50 W
minimum switching capacity24 mW
operating rate<= 360 cycles/hour under load
<= 18000 cycles/hour no-load
mechanical durability10000000 cycles
electrical durability60000 cycles, 6 A at 250 V, AC-1 C/O
operating time5 ms reset
12 ms
protection categoryRT III
test levelsLevel A group mounting
operating positionAny position
width5 mm
height28 mm
depth18.5 mm
terminals description ISO n°1(A1-A2)CO
(11-12-14)OC
net weight0.0054 kg
load current6 A at 250 V AC 0.5 mm mounting distance
average coil consumption0.21 W
drop-out voltage threshold>= 0.05 Uc
safety reliability dataB10d = 60000
mounting supportSocket or PCB
device presentationComplete product

Environment

dielectric strength1000 V AC between contacts
4000 V AC between coil and contact
standardsUL 508
CSA C22.2 No 14
EN/IEC 61810-1
product certificationsEAC
CSA
UL
ambient air temperature for storage-40…70 °C
vibration resistance+/- 1 mm (f= 10…55 Hz) conforming to EN/IEC 60068-2-6
IP degree of protectionIP40 conforming to EN/IEC 60529
shock resistance5 gn (duration = 11 ms) for not operating conforming to EN/IEC 60068-2-27
5 gn (duration = 11 ms) for in operation conforming to EN/IEC 60068-2-27
ambient air temperature for operation-40…55 °C
Questions