Relay CAD32M7

  • Model: 004.017.114
Relay CAD32M7
Manufacturer: Schneider Electric
Barcode: 3389110401424
TeSys D Control relay CAD32M7 is intended for 35 mm DIN rail installation. Can also be mounted on a panel by means of M4 screws.
3 normally open (3NO) and 2 normally closed (2NC) contacts.
Control circuit voltage 220V 50/60Hz.
Screw clamp terminals. Connection of cables with cross-section 1...4 mm2 is allowed.
Conforms to the following standards: IEC60947-5-1, NF C 63-140, VDE 0660, BS 4794, EN60947-5.

Main

rangeTeSys
product nameTeSys CAD
product or component typeControl relay
device short nameCAD
contactor applicationControl circuit

Complementary

utilisation categoryDC-13
AC-14
AC-15
pole contact composition3 NO + 2 NC
[Ue] rated operational voltage≤ 690 V AC 25...400 Hz
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage220 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
[Ith] conventional free air thermal current10 A (at 60 °C)
Irms rated making capacity140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
[Icw] rated short-time withstand current100 A - 1 s
120 A - 500 ms
140 A - 100 ms
associated fuse rating10 A gG conforming to IEC 60947-5-1
[Ui] rated insulation voltage600 V UL certified
600 V CSA certified
690 V conforming to IEC 60947-5-1
mounting supportPlate
Rail
connections - terminalsScrew clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
tightening torque1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
operating time12...22 ms coil energisation and NO closing
4...12 ms coil de-energisation and NO opening
4...19 ms coil energisation and NC opening
6...17 ms coil de-energisation and NC closing
mechanical durability30 Mcycles
maximum operating rate180 cyc/mn
inrush power in VA70 VA 50 Hz (at 20 °C)
hold-in power consumption in VA8 VA 50 Hz (at 20 °C)
minimum switching voltage17 V
minimum switching current5 mA
non-overlap time1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
insulation resistance> 10 MOhm
mechanical robustnessShocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
height77 mm
width45 mm
depth84 mm
net weight0.58 kg

Environment

standardsBS 4794
EN 60947-5
IEC 60947-5-1
NF C 63-140
VDE 0660
product certificationsCSA
UL
IP degree of protectionIP2x front face conforming to VDE 0106
protective treatmentTH conforming to IEC 60068
ambient air temperature for operation-40…60 °C
60…70 °C with derating
ambient air temperature for storage-60…80 °C
operating altitude0...3000 m

Dimensions and scheme

Relay dimensions and scheme
Questions