Digital temperature relay TR-100

  • Model: 026.004.114
Digital temperature relay TR-100
Country of origin: Россия
TR-100 is used to measure and control device temperature via four RT100 sensors connected in a two- or-three-wire circuit, with subsequent indication of the temperature on the display and alarm signaling in case of any parameters being outside the set range.
$83.97
 pcs
It can be used to protect:
•  engines and generators;
•  three-phase air transformers with additional core or environment temperature control.

TR-100 can use any voltage between 24 and 225V, regardless of the polarity.

The following thermal sensors can be used by TR-100:
•  PT100 – platinum sensor with nominal resistance of 100 Ohm at 0 °С;
•  PT1000 – platinum sensor with nominal resistance of 1000 Ohm at 0 °С;
•  KTY83 – silicon sensor with nominal resistance of 1000 Ohm at 25 °С;
•  KTY84 – silicon sensor with nominal resistance of 1000 Ohm at 100 °С;
•  PTC (1, 3, 6 serial connection), cold resistance of 20-250 Ohm.

Technical Specifications

Supply power, V24 - 260 AC/DC
Recommended fuse for equipment protection, А1 - 2
Thermal transducersPT100, PT1000, KTY83, KTY84, PTC
Connectable transducers, pcs.1 - 4*
Method of hardwire2 / 3 wired
Wire length of sensor (depending on method of hardwire), m:2 wired up to 5
3 wired up to100
Amount of output relay, pcs.4
Date-hold time, years, not less then15
Temperature measurement error, °С± 3
Temperature measurement range, °Сfrom - 40 to +240
Output relay testYes
Indication testYes
RS-485 MODBUS RTUTo order
Time measurement, sec.≤ 2
Degree of protection:
- body
- terminal block

ІР30
ІР20
Climatic executionY3.1
Power input (power load), VA, no more than4.0
Weight, kg, no more then0.370
Dimensions, mm90 х 139 х 63
Commutation life of the output contacts:
- under 10A 250V AC, times, not less than
- under 10А 24V DC, times, not less than

100 mil.
100 mil.
Operation temperature range, °Сfrom -40 to +55
Storage temperature, °Сfrom -50 to +60
Montage to standard 35mm mounting frameto standard 35 mm mounting frame
Free position in space
* note – PTC transducers can be connected as serial connection (1, 3, 6 pc.)

Characteristic of output contacts

Operation modeMax. current at U~250 VMax. powerMax. voltageMax. current at U DC=30 V
cosφ = 1.010 A2500 VA440 V3 A

Dimensions

Digital temperature relay TR-100
Questions