reset time | 1500 ms time delay |
maximum switching voltage | 250 V AC 250 V DC |
minimum switching current | 10 mA at 5 V DC |
maximum switching current | 5 A AC 5 A DC |
supply voltage limits | 183…528 V AC |
control circuit voltage limits | - 12 % + 10 % Un |
power consumption in VA | 0…22 VA at 400 V AC 50 Hz |
control circuit frequency | 50...60 Hz +/- 10 % |
output contacts | 1 C/O |
nominal output current | 5 A |
measurement voltage limits | 183…528 V AC |
hysteresis | 2 % |
delay at power up | 650 ms |
maximum measuring cycle | 150 ms measurement cycle as true rms value |
threshold adjustment voltage | -2...-17 % in the range 220 V AC +2...+17 % in the range 480 V AC -2...-12 % in the range 208 V AC 2...20 % of Un selected |
voltage range | 208...480 V phase to phase |
adjustment of asymmetry threshold | 5...15 % of Un selected |
repeat accuracy | 0.5 % for input and measurement circuit 3 % for time delay |
measurement error | < 0.05 %/°C with temperature variation < 1 % over the whole range with voltage variation< div> |
phase failure sensitivity | 0.7 Un |
response time | < 200 ms (in the event of a fault)< div> |
marking | CE |
overvoltage category | III conforming to IEC 60664-1 |
insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 > 500 MOhm at 500 V DC conforming to IEC 60664-1 |
[Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
supply frequency | 50/60 Hz +/- 10 % |
operating position | Any position without derating |
connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end |
tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
housing material | Self-extinguishing plastic |
local signalling | LED (green) for power ON LED (yellow) for relay ON |
mounting support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
electrical durability | 100000 cycles |
mechanical durability | 30000000 cycles |
operating rate | ≤ 360 operations/hour full load |
utilisation category | AC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 |
safety reliability data | MTTFd = 502.2 years B10d = 470000 |
width | 17.5 mm |
net weight | 0.13 kg |