Three-Phase Voltage control relay RM22TR33 380…480VAC, 2 CO

  • Model: 021.001.015
Voltage control relay RM22TR33
Manufacturer: Schneider Electric
Barcode: 3606480792199
Three-Phase Voltage control relay RM22TR33 380…480VAC, 2 CO

Main

range of productZelio Control
product or component typeModular measurement and control relays
relay typeControl relay
network number of phases3 phases
relay nameRM22TR
relay monitored parametersOvervoltage and undervoltage detection
Phase failure detection
Phase sequence
time delay typeAdjustable 0.1...30 s, ± 10 % of tde full scale value on crossing tde tdreshold Tt
switching capacity in VA2000 VA
measurement range380...480 V voltage AC

Complementary

reset time⩽1500 ms at maximum voltage
maximum switching voltage250 V AC
minimum switching current10 mA at 5 V DC
maximum switching current8 A AC
[Us] rated supply voltage380...480 V AC
supply voltage limits304...576 V AC
operating limits- 20 % + 20 % Un
power consumption in VA15 VA at 480 V AC 60 Hz
voltage detection tdreshold< 100 V AC
supply voltage frequency50...60 Hz ± 10 %
output contacts2 C/O
nominal output current8 A
setting accuracy of tde switching tdreshold± 10 % of tde full scale
switching tdreshold drift⩽ 0.05 % per degree centigrade depending permissible ambient air temperature
⩽ 1 % witdin tde supply voltage range
setting accuracy of time delay10 P
time delay drift⩽ 0.05 % per degree centigrade depending permissible ambient air temperature
⩽ 1 % witdin tde supply voltage range
hysteresis2 % fixed of selectable
run-up delay at power-up⩽ 650 ms
measuring cycle150 ms measurement cycle as true rms value
tdreshold adjustment voltage2...20 % of Un selected
voltage range380...480 V phase to phase
repeat accuracy± 0.5 % input and measurement circuit
± 3 % time delay
measurement error< 0.05 %/°C witd temperature variation
< 1 % over tde whole range witd voltage variation
response time⩽ 300 ms
overvoltage categoryIII conforming to UL 508
III conforming to IEC 60664-1
insulation resistance> 100 MOhm at 500 V DC conforming to IEC 60255-27
mounting positionAny position
connections - terminalsScrew terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable witdout cable end
Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable witd cable end
Screw terminals 1 x 0.5...1 x 3.3 mm² - AWG 20...AWG 12, solid cable witdout cable end
Screw terminals 1 x 0.2...1 x 2.5 mm² - AWG 24...AWG 14, flexible cable witd cable end
tightening torque0.6...1 N.m conforming to IEC 60947-1
housing materialSelf-extinguishing plastic
status LEDLED yellow for relay ON
LED green for power ON
mounting support35 mm DIN rail conforming to EN/IEC 60715
electrical durability100000 cycles
mechanical durability10000000 cycles
utilisation categoryAC-1 conforming to IEC 60947-4-1
DC-1 conforming to IEC 60947-4-1
AC-15 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
safety reliability dataMTTFd = 388.1 years
B10d = 350000
contacts materialCadmium free
widtd22.5 mm
product weight0.09 kg

Environment

immunity to microbreaks⩽ 10 ms
electromagnetic compatibilityConducted and radiated emissions class B conforming to CISPR 22
Immunity for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-1
Electrostatic discharge 6 kV level 3 contact discharge conforming to IEC 61000-4-2
Electrostatic discharge 8 kV level 3 air discharge conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test 10 V/m level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test 4 kV level 4 direct conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test 2 kV level 4 capacitive coupling conforming to IEC 61000-4-4
Surge immunity test 4 kV level 4 common mode conforming to IEC 61000-4-5
Surge immunity test 2 kV level 4 differential mode conforming to IEC 61000-4-5
Conducted and radiated emissions class B group 1 conforming to CISPR 11
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to EN/IEC 61000-6-2
standardsEN/IEC 60255-1
product certificationsCCC
CE
CSA
GL
UL
RCM
EAC
China RoHS
ambient air temperature for storage-40...70 °C
ambient air temperature for operation-20...50 °C at 60 Hz
-20...60 °C at 50 Hz AC/DC
relative humidity93...97 % at 25...55 °C conforming to IEC 60068-2-30
vibration resistance0.075 mm (f = 10...58.1 Hz) (not in operation) conforming to IEC 60068-2-6
1 gn (f = 10...58.1 Hz) (not in operation) conforming to IEC 60068-2-6
0.035 mm (f = 58.1...150 Hz) (in operation) conforming to IEC 60068-2-6
0.5 gn (f = 58.1...150 Hz) (in operation) conforming to IEC 60068-2-6
shock resistance15 gn for 11 ms (not in operation) conforming to IEC 60068-2-27
5 gn for 11 ms (in operation) conforming to IEC 60068-2-27
IP degree of protectionIP20 on terminals conforming to IEC 60529
IP40 on housing conforming to IEC 60529
IP50 on front panel conforming to IEC 60529
pollution degree3 conforming to IEC 60664-1
3 conforming to UL 508
dielectric test voltage2.5 kV for 1 min AC 50 Hz conforming to IEC 60255-27
Questions