Pump station controller MСK-108

  • Model: 026.004.108
Pump station controller MСK-108
Country of origin: Россия
Pump station controller MСK-108 is designed to create the process automation systems related to the control and maintainance of the set level of liquids in various containers by controlling the electric motor (motors) of one or two pumps.
$71.28
 pcs

The maintainance of the set level of liquids is provided by the controlling:

•  built-in pump relay – at single-phase motors with capacity up to 1 kW;
•  coil of magnetic starter (contactor) – at three-phase motor or single-phase engine with capacity of more than 1 kW.

The MСK-108 controls the electric motor (motors) of one or two pumps in automatic mode, using one of the built-in algorithms.

The MСK-108 provides the operation with liquids of different electrical conductivity – tap or contaminated water, milk and food (weakly acid, alkaline, etc.).

General specification

Purpose of deviceControl and distribution equipment
Rated operating regimecontinuous
Protection classIP20
Electric shock protection classII
Climatic versionNС 3.1
Allowable pollution ratingII
Overvoltage categoryII
Rated insulation overvoltage, V450
Rated impulse withstand voltage, kV2.5
Connecting terminals wire section, mm²0.5-2
Tightening torque of terminal screws, N*m0.4

Technical Specifications

Rated supply voltage: single-phase220/230 V
Voltage, at which operability is maintained:
- minimum, V
- maximum, V

130
265
Mains frequency, Hz48-62
Analog Inputs:
- input for connecting level sensor (of pressure)
- general for level sensors (of pressure)

4
1
Main outputs:
- pump relay - make contact for controlling electric motor starter - 10 A 250 V at cos φ=1, piece
- functional relay – transfer contact - 10 A 250 V at cos φ=1, piece

1
1
Controlled environment resistance for conduction-measuring sensor, kiloohm, not more than450
Power consumption (under pressure), not more than, W3.3
Weight, not more than, kg0.2
Overall dimensions, mm90 x 52 x 69
Installationstandard 35 mm DIN rail
The device preserves functionality in any position within the space
Casing material – self-extinguishing plastic

Characteristics of output terminals of integrated relays

Operation modeMax. current at U~250 VN of tripping х1000Max. commutated powerMax. current at Uconst=30 V
cosφ = 0.4
cosφ = 1.0
5 A
10 A
50
100
4000 VA3 A

Dimensions

Dimensions pump station controller MСK-108