The UBZ-305 can operate in the mains with isolated neural as well as with solidly-grounded neutral.
The device is equipped with DIN rail.
The UBZ provides continuous control of the mains voltage parameters and RMS phase (line) currents of the three-phase electric equipment of 380V 50Hz, as well as the electric motor insulation resistance test.
The UBZ provides electric motor protection in the following cases:
• when the mains voltage is of poor quality (unacceptable voltage fluctuations, phase interruption, violation of phase sequence and phase coincidence, phase/line voltage imbalance, decrease of mains frequency below the specified one and (or) increase of mains frequency above the set one);
• when mechanical overloads (symmetrical phase/line current overloads) occur;
• when reverse sequence of the current threshold occurs;
• when phase current imbalance (without overload) occurs that is induced by the insulation fault inside the motor and/or the lead cable (comparison of current imbalance factor with voltage imbalance factor based on negative sequence);
• when motor torque is lost (“dry run” for pumps) – protection based on the minimum inrush and/or operating current;
• when start delays or locked rotor occurs;
• when insulation level between the fixed coil (stator) and frame is abnormally low (test before motor start).
• when stator winding ground fault takes place during operation – ground leakage current protection;
• when motor thermal overload occurs;
• when winding overheating occurs (winding temperature is measured by the integrated temperature sensors, or frame temperature is measured by the external temperature sensors).
General specification
Application of the unit | Switchgear and control-gear; induction motor protection control |
Design (installation) type | DIN rail 35 mm |
Protection level | IP20 |
Climatic version | UHL 3.1 |
Operating temperature range* | from -20 to +55 °C |
Contamination level | II |
Overvoltage category | II |
Rated voltage of insulation | 450 V |
Rated impulse withstand voltage | 2.5 kV |
Electric shock protection class | II |
Wire cross section for connection to terminals | 0.5-2 mm² |
Torque for terminal screws | 0.4 N*M |
*Note: It is allowed UBZ operation at temperatures from minus 35 to minus 20°С; in this case the readings on display can be not available. |
Technical Specifications
Operating supply voltage, three-phase | 380 V, 50 Hz |
Mains frequency, Hz | 48-62 |
Rated current of CT, A | 5 |
Voltage hysteresis, (phase/line), V | 10/17 |
Thermal hysteresis, % of accumulated heat at shutdown | 33 |
Determination accuracy of trip threshold for current, not more, in % of rated value | 2 |
Determination accuracy of trip threshold for voltage, not more, V | 3 |
Determination accuracy of out-of-phase voltage, not more, V | 3 |
Voltage when maintaining serviceability: - phase voltage, when powered by one phase and zero wire is connected, not less, V - line voltage, when powered by three phases, not more, V | 180 450 |
Main outputs: - load relay – two groups of changeover contacts to control the electric motor starter – 8A, 250 V at cos φ=1; - functional relay – one group of changeover contacts - 16A, 250V at cos φ=1 (function of the relay is set by the user). | |
Analog inputs: - input to connect temperature transmitter (types: Pt100, Ni100, Ni120), pc.; - input to connect temperature transmitter of PTC-1000 type, pc.; - three analog inputs for standard CT with 5A output (T-0.66 type or similar), pc.; - input to connect differential current transformer (zero sequence transformer) pc.; - input to measure current of 0-20 mA, pc.; - input to measure voltage of 0–10 V, pc.. | 1 1 3 1 1 1 |
Permit according to temperature of temperature transmitters, °C | 1 |
Power consumption (under load), VA, not more | 5.0 |
Weight, kg, no more than | 0.34 |
Overall dimensions | 91 х 157 х 58 mm |
Position in space | free |
Housing material | self-extinguishing plastic |
Characteristics of output terminals of integrated relays
Relay | Max. current at U~250 V | Number of actuations х1000 | Max. switching power | Max. continuous boosting AC / DC voltage | Max. current at Uconst=30 V |
---|
Functional relay cosφ = 0.4 cosφ = 1.0 | 5 A 16 A | 100 100 | 4000 VA | 440/300 V | 5 A |
Load relay cosφ = 0.4 cosφ = 1.0 | 2 A 8 A | 100 100 | 2000 VA | 460 V | 3 A |
Dimensions