Power supply unit Quint-PS/1AC/12DC/15 2866718

  • Model: 026.001.022
Power supply unit Quint-PS/1AC/12DC/15 2866718
Manufacturer: Phoenix Contact
Barcode: 4046356307888
Power supply Quint-PS/1AC/12DC/15 2866718 for DIN rail mounting with SFB (Selective Fuse Breaking) technology.
• Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently;
• Fast tripping of standard circuit breakers with dynamic power reserve SFB technology with up to 6 timesthe nominal current for 12ms;
• For superior system availability;
• Preventive function monitoring.
$402.58
 pcs

Technical data

Output data
Nominal output voltage12VDC ±1%
Setting range of the output voltage5VDC...18VDC
Output current15А (-25°C...+60°C)
16А (with Power Boost, -25°C...+40°C, permanent)
60A (SFB technology, 12ms)
60А (Uin≥ 100VАС)
Derating60°C...70°C (2,5% / K)
Connection in parallelyes, for redundancy and increased capacity
Connection in seriesyes
Control deviation< 1% (change in load, static 10%...90%)
< 2% (change in load, dynamic 10%...90%)
< 0,1% (change in input voltage ±10%)
Residual ripple< 10 mVpp (with nominal values)
Max power dissipation NO-load5W
Max power loss nominal load21W
Input data
Nominal input voltage range100VAC...240VAC
Input voltage range85V...264V АС (50/60Hz)
90V...350V DC
Short-term input voltage300VAC
AC frequency range45Hz...65Hz
Inrush surge current< 15A (typical)
Power failure bypass> 65ms (120VAC)
> 65 ms (230VAC)
Input fuse6,3А (slow-blow, internal)
Choice of suitable fuses10А...16А (АС: characteristics B, C, D, K)
Type of protectiontransient surge protection
Protective circuit/componentvaristor
Ganaral data
Dimensions (WxHxD)60 x 130 x 125 mm
Efficiency (for 230VAC and nominal values)> 89 %
Insulation voltage input/output4 kVAC (type test)
2 kVAC (routine test)
Protection classI
> 570000 h (40°C)
Mounting positionhorizontal DIN rail NS 35, EN 60715
Assembly instructionsalignable: 5 mm horizontally, 15 mm next to active components, 50 mm vertically
Electromagnetic compatibilityconformance with EMC directive 2004/108/EC
Surge voltage categoryIII
Degree of protectionIP20
Ambient temperature (operation)-25°C...+70°C
Ambient temperature (storage/transport)-40°C...+85°C
Max permissible relative humidity (operation)≤ 95% (at 25°C, non-condensing)
Connection data
Connection methodpluggable screw connection
Solid conductor cross-section/AWG0,2...2,5mm2/16...12
Stranded conductor cross-section/AWG0,2...2,5mm2/16...12
Stripping length7 mm
Screw threadМ3

Block diagram

Power supply 2866718 Phoenix Contact
Questions