Power supply Phaseo ABL8RPS24050 24 VDC, 5А

  • Model: 026.021.004
Power supply Phaseo ABL8RPS24050
Manufacturer: Schneider Electric
Barcode: 3389119405614
Regulated SMPS Phaseo ABL8RPS24050 1 or 2-phase - 100..500 V / 24 V -5 A

Specifications

Main
range of productPhaseo
product or component typePower supply
power supply typeRegulated switch mode
input voltage100 … 120 V AC single phase, terminal(s): N-L1
200 … 500 V AC phase to phase, terminal(s): L1-L2
output voltage24 V DC
rated power in W120 W
provided equipmentPower factor correction filter conforming to IEC 61000-3-2
power supply output current5 A
output protection typeAgainst overload, protection technology: manual or automatic reset
Against overvoltage, protection technology: 30 … 32 V, manual reset
Against short-circuits, protection technology: manual or automatic reset
Against undervoltage, protection technology: tripping if U < 21.6 V
Thermal, protection technology: automatic reset
ambient air temperature for operation50 … 60 °C with
-25 … 50 °C without
Complementary
input voltage limits170 … 550 V
85 … 132 V
network frequency47 … 63 Hz
inrush current30 A for 2 ms
cos phi0.51 at 240 V
0.59 at 120 V
efficiency87 %
output voltage limits24 … 28.8 V adjustable
power dissipation in W15.5 W
line and load regulation1 … 3 %
holding time⩾ 120 ms at 400 V
⩾ 20 ms at 100 V
⩾ 40 ms at 240 V
permissible temporary current boost1.5 x In for 4 s
connections - terminalsScrew type terminals for input connection, connection capacity: 3 x 0.5 … 3 x 4 mm² AWG 22 … AWG 12
Screw type terminals for input ground connection, connection capacity: 1 x 0.5 … 1 x 4 mm² AWG 22 … AWG 12
Screw type terminals for output connection, connection capacity: 4 x 0.5 … 4 x 4 mm² AWG 22 … AWG 12
Screw type terminals for output ground connection, connection capacity: 1 x 0.5 … 1 x 4 mm² AWG 22 … AWG 12
Removable screw terminal block for diagnostic relay, connection capacity: 2 x 2.5 mm²
markingCE
mounting support35 x 15 mm symmetrical DIN rail
35 x 7.5 mm symmetrical DIN rail
operating positionVertical
operating altitude2000 m
output couplingParallel
Series
name of testHarmonic current emission conforming to EN/IEC 61000-3-2
Conducted emissions on the power line conforming to EN 55022 Class B
Electrostatic discharges conforming to EN/IEC 61000-4-2
Induced electromagnetic field conforming to EN/IEC 61000-4-6
Magnetic field conforming to EN 61000-4-8
Primary outage conforming to IEC 61000-4-11
Radiated electromagnetic field conforming to EN/IEC 61000-4-3
Radiated emissions conforming to EN 55022 Class B
Rapid transient conforming to IEC 61000-4-4
Surge conforming to EN/IEC 61000-4-5
status LED1 LED green for output voltage
1 LED orange for input voltage
depth125 mm
height143 mm
width56 mm
product weight0.7 kg
Environment
product certificationsCCSAus
UL
KC
standardsUL 508
CSA C22.2 No 60950-1
environmental characteristicEMC conforming to EN 61000-6-1
EMC conforming to EN 61000-6-3
EMC conforming to EN/IEC 61000-6-2
EMC conforming to EN/IEC 61000-6-4
EMC conforming to EN/IEC 61204-3
Safety conforming to EN/IEC 60950-1
Safety conforming to EN/IEC 61204-3
Safety conforming to SELV
IP degree of protectionIP20 conforming to EN/IEC 60529
ambient air temperature for storage-40 … 70 °C
relative humidity0 … 90 % during operation
0 … 95 % in storage
overvoltage categoryClass I conforming to VDE 0106-1
dielectric strengthBetween input and ground
Between output and ground
Between input and output
MTBF reliability915000 H at 100 V AC with UTE C80-810 calculation method
950000 H at 200 … 500 V AC with UTE C80-810 calculation method