Main |
---|
range of product | Phaseo |
product or component type | Power supply |
power supply type | Regulated switch mode |
input voltage | 100 … 120 V AC single phase, terminal(s): N-L1 200 … 500 V AC phase to phase, terminal(s): L1-L2 |
output voltage | 24 V DC |
rated power in W | 120 W |
provided equipment | Power factor correction filter conforming to IEC 61000-3-2 |
power supply output current | 5 A |
output protection type | Against overload, protection technology: manual or automatic reset Against overvoltage, protection technology: 30 … 32 V, manual reset Against short-circuits, protection technology: manual or automatic reset Against undervoltage, protection technology: tripping if U < 21.6 V Thermal, protection technology: automatic reset |
ambient air temperature for operation | 50 … 60 °C with -25 … 50 °C without |
Complementary |
---|
input voltage limits | 170 … 550 V 85 … 132 V |
network frequency | 47 … 63 Hz |
inrush current | 30 A for 2 ms |
cos phi | 0.51 at 240 V 0.59 at 120 V |
efficiency | 87 % |
output voltage limits | 24 … 28.8 V adjustable |
power dissipation in W | 15.5 W |
line and load regulation | 1 … 3 % |
holding time | ⩾ 120 ms at 400 V ⩾ 20 ms at 100 V ⩾ 40 ms at 240 V |
permissible temporary current boost | 1.5 x In for 4 s |
connections - terminals | Screw type terminals for input connection, connection capacity: 3 x 0.5 … 3 x 4 mm² AWG 22 … AWG 12 Screw type terminals for input ground connection, connection capacity: 1 x 0.5 … 1 x 4 mm² AWG 22 … AWG 12 Screw type terminals for output connection, connection capacity: 4 x 0.5 … 4 x 4 mm² AWG 22 … AWG 12 Screw type terminals for output ground connection, connection capacity: 1 x 0.5 … 1 x 4 mm² AWG 22 … AWG 12 Removable screw terminal block for diagnostic relay, connection capacity: 2 x 2.5 mm² |
marking | CE |
mounting support | 35 x 15 mm symmetrical DIN rail 35 x 7.5 mm symmetrical DIN rail |
operating position | Vertical |
operating altitude | 2000 m |
output coupling | Parallel Series |
name of test | Harmonic current emission conforming to EN/IEC 61000-3-2 Conducted emissions on the power line conforming to EN 55022 Class B Electrostatic discharges conforming to EN/IEC 61000-4-2 Induced electromagnetic field conforming to EN/IEC 61000-4-6 Magnetic field conforming to EN 61000-4-8 Primary outage conforming to IEC 61000-4-11 Radiated electromagnetic field conforming to EN/IEC 61000-4-3 Radiated emissions conforming to EN 55022 Class B Rapid transient conforming to IEC 61000-4-4 Surge conforming to EN/IEC 61000-4-5 |
status LED | 1 LED green for output voltage 1 LED orange for input voltage |
depth | 125 mm |
height | 143 mm |
width | 56 mm |
product weight | 0.7 kg |
Environment |
---|
product certifications | CCSAus UL KC |
standards | UL 508 CSA C22.2 No 60950-1 |
environmental characteristic | EMC conforming to EN 61000-6-1 EMC conforming to EN 61000-6-3 EMC conforming to EN/IEC 61000-6-2 EMC conforming to EN/IEC 61000-6-4 EMC conforming to EN/IEC 61204-3 Safety conforming to EN/IEC 60950-1 Safety conforming to EN/IEC 61204-3 Safety conforming to SELV |
IP degree of protection | IP20 conforming to EN/IEC 60529 |
ambient air temperature for storage | -40 … 70 °C |
relative humidity | 0 … 90 % during operation 0 … 95 % in storage |
overvoltage category | Class I conforming to VDE 0106-1 |
dielectric strength | Between input and ground Between output and ground Between input and output |
MTBF reliability | 915000 H at 100 V AC with UTE C80-810 calculation method 950000 H at 200 … 500 V AC with UTE C80-810 calculation method |