Variable speed drive ATV212HU75N4

  • Model: 027.021.061
Variable speed drive ATV212HU75N4
Manufacturer: Schneider Electric
The Altivar ATV212HU75N4 is a variable speed drive for 3-phase asynchronous motors 7.5kW. It is specifically intended for the most commonly encountered fluid management applications in tertiary sector buildings (HVAC): heating, ventilation, air conditioning and pumping. Due to its eco-energy based design, energy savings of up to 70% can be achieved compared to a traditional control system.

Main

range of productAltivar 212
product or component typeVariable speed drive
device short nameATV212
product destinationAsynchronous motors
product specific applicationPumps and fans in HVAC
assembly styleWith heat sink
network number of phases3 phases
motor power kW7.5 kW
motor power hp10 hp
[Us] rated supply voltage380...480 V - 15...10 %
supply voltage limits323…528 V
supply frequency50...60 Hz - 5...5 %
EMC filterClass C2 EMC filter integrated
line current11.7 A at 480 V
14.7 A at 380 V

Complementary

apparent power12.2 kVA at 380 V
prospective line Isc22 kA
continuous output current16 A at 380 V
16 A at 460 V
maximum transient current17.6 A for 60 s
speed drive output frequency0.5…200 Hz
nominal switching frequency12 kHz
switching frequency6...16 kHz adjustable
12...16 kHz with derating factor
speed range1…10
speed accuracy+/- 10 % of nominal slip 0.2 Tn to Tn
torque accuracy+/- 15 %
transient overtorque120 % of nominal motor torque +/- 10 % for 60 s
asynchronous motor control profileVoltage/frequency ratio - Energy Saving, quadratic U/f
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Flux vector control without sensor, standard
Voltage/frequency ratio, 5 points
Voltage/frequency ratio, 2 points
regulation loopAdjustable PI regulator
motor slip compensationNot available in voltage/frequency ratio motor control
Automatic whatever the load
Adjustable
local signalling1 LED (red) for DC bus energized
output voltage≤ power supply voltage
isolationElectrical between power and control
type of cableWithout mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
electrical connectionVIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
L1/R, L2/S, L3/T: terminal 16 mm² / AWG 6
tightening torque0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
2.5 N.m, 22 lb.in (L1/R, L2/S, L3/T)
supplyInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, < 10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), < 200 A, protection type: overload and short-circuit protection
analogue input number2
analogue input typeVIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm
VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits
sampling duration2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog
response timeFM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
accuracy+/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °C
linearity errorVIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
FM: +/- 0.2 % for output
analogue output number1
analogue output typeFM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits
discrete output number2
discrete output typeConfigurable relay logic: (FLA, FLC) NO - 100000 cycles
Configurable relay logic: (FLB, FLC) NC - 100000 cycles
Configurable relay logic: (RY, RC) NO - 100000 cycles
minimum switching current3 mA at 24 V DC for configurable relay logic
maximum switching current5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
discrete input typeF programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
discrete input logicPositive logic (source) (F, R, RES), ≤ 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), ≤ 10 V (state 1)
acceleration and deceleration rampsLinear adjustable separately from 0.01 to 3200 s
Automatic based on the load
braking to standstillBy DC injection
protection typeOverheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overvoltages on the DC bus: drive
Break on the control circuit: drive
Against exceeding limit speed: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor
Motor phase break: motor
With PTC probes: motor
dielectric strength3535 V DC between earth and power terminals
5092 V DC between control and power terminals
insulation resistance>= 1 mOhm 500 V DC for 1 minute
frequency resolutionDisplay unit: 0.1 Hz
Analog input: 0.024/50 Hz
communication port protocolAPOGEE FLN
LonWorks
BACnet
METASYS N2
Modbus
connector type1 open style
1 RJ45
physical interface2-wire RS 485
transmission frameRTU
transmission rate9600 bps or 19200 bps
data format8 bits, 1 stop, odd even or no configurable parity
type of polarizationNo impedance
number of addresses1…247
communication serviceMonitoring inhibitable
Read holding registers (03) 2 words maximum
Write multiple registers (16) 2 words maximum
Write single register (06)
Read device identification (43)
Time out setting from 0.1 to 100 s
option cardCommunication card for LonWorks
operating positionVertical +/- 10 degree
width180 mm
height232 mm
depth170 mm
net weight6.45 kg
power dissipation in W291 W
air flow100 m3/h
functionalityMid
specific applicationHVAC
IP degree of protectionIP21
Variable speed drive application selectionBuilding - HVAC Compressor for scroll
Building - HVAC Fan
Building - HVAC Pump
Motor power range AC-37…11 kW at 380…440 V 3 phases
7…11 kW at 480…500 V 3 phases
motor starter typeVariable speed drive

Environment

electromagnetic compatibilityElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
pollution degree3 conforming to IEC 61800-5-1
IP degree of protectionIP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1
IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529
IP21 conforming to EN/IEC 61800-5-1
IP21 conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
vibration resistance1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8
shock resistance15 gn for 11 ms conforming to IEC 60068-2-27
environmental characteristicClasses 3C1 conforming to IEC 60721-3-3
Classes 3S2 conforming to IEC 60721-3-3
noise level51 dB conforming to 86/188/EEC
operating altitude1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
≤ 1000 m without derating
relative humidity5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3
ambient air temperature for operation-10…40 °C (without derating)
40…50 °C (with derating factor)
ambient air temperature for storage-25…70 °C
standardsEN 61800-3
EN 61800-3 environments 1 category C1
IEC 61800-3 category C3
IEC 61800-5-1
IEC 61800-3 category C2
IEC 61800-3 environments 1 category C2
EN 61800-3 environments 2 category C2
EN 61800-3 environments 1 category C2
EN 61800-3 category C2
EN 61800-3 category C3
EN 61800-3 environments 2 category C3
IEC 61800-3 environments 1 category C3
UL Type 1
IEC 61800-3 environments 2 category C2
EN 61800-3 environments 1 category C3
IEC 61800-3 environments 2 category C1
EN 55011 class A group 1
EN 61800-3 environments 2 category C1
EN 61800-5-1
IEC 61800-3 environments 2 category C3
IEC 61800-3
IEC 61800-3 environments 1 category C1
product certificationsC-Tick
NOM 117
UL
CSA
markingCE
Questions
WhatsAppTelegramViberVKemail