Contactor iCT A9C22813

  • Model: 004.016.028
  • photo 3
  • photo 4
Contactor iCT A9C22813
Manufacturer: Schneider Electric
Barcode: 3606480088650
Contactor A9C22813 in iCT series is used in AC circuits for remote control under different systems.

Main

range of productActi9
product nameActi9 iCT
product or component typeContactor
device short nameICT
device applicationMotor-heating-lighting
Poles3P
[Ie] rated operational current16 A AC-7A
6 A AC-7B
pole contact composition3 NO
network typeAC
control typeRemote control
[Uc] control circuit voltage220...240 V AC 50 Hz

Complementary

network frequency50 Hz
[Ue] rated operational voltage400 V AC 50 Hz
maximum power1.6 W at 400 V AC
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV
control signal typeMaintained
switching frequency100 switching operations/day
local signallingAction indicator
hold-in power consumption in VA4.6 VA
inrush power in VA34 VA
mounting modeClip-on
mounting support35 mm symmetrical DIN rail
9 mm pitches4
height81 mm
width36 mm
depth60 mm
colourWhite
mechanical durability1000000 cycles
electrical durability100000 cycles IEC/EN 61095 16 A 50 Hz AC-7A
30000 cycles IEC/EN 61095 6 A 50 Hz AC-7B
30000 cycles IEC/EN 61095 50 Hz AC-7C
100000 cycles EN/IEC 60947-4-1 50 Hz AC-1
30000 cycles EN/IEC 60947-4-1 50 Hz AC-3
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b
connections - terminalsControl circuit: tunnel type terminals2 cable(s) 1.5 mm² rigid
Power circuit: tunnel type terminals1 cable(s) 1…4 mm² flexible
Power circuit: tunnel type terminals1 cable(s) 1.5…6 mm² rigid
Control circuit: tunnel type terminals1 cable(s) 1.5…2.5 mm² rigid
Control circuit: tunnel type terminals2 cable(s) 1.5…2.5 mm² flexible
tightening torqueControl circuit: 0.8 N.m
Power circuit: 0.8 N.m
product compatibilityIACTs
compatibility codeICT
market segmentResidential
Small commercial

Environment

standardsIEC/EN 61095
noise level30 dB
heat dissipation1.6 W
IP degree of protectionIP20
pollution degree2
tropicalisation2 conforming to EN 60947-4-1
2 conforming to EN 61095
2 conforming to IEC 1095
relative humidity95 % at 55 °C
operating altitude2000 m
ambient air temperature for operation-5…60 °C
ambient air temperature for storage-40…70 °C

Dimensions

Contactor А9С22813 dimensions
Questions
WhatsAppTelegramViberVKemail