Miniature contactor LP4K0910JW3

  • Model: 004.014.391
Miniature contactor LP4K0910JW3
Manufacturer: Schneider Electric
Barcode: 3389110500509

Main

range of productTeSys K
rangeTeSys
product or component typeContactor
device short nameLP4K
contactor applicationResistive load
Motor control
utilisation categoryAC-4
AC-1
AC-3
poles description3P
pole contact composition3 NO
[Ie] rated operational current20 A (at < 50 °C) at ≤ 440 V AC AC-1 for power circuit
9 A at ≤ 440 V AC AC-3 for power circuit
16 A (at < 70 °C) at 690 V AC AC-1 for power circuit
auxiliary contact composition1 NO

Complementary

coil technologyBuilt-in bidirectional peak limiting diode suppressor
auxiliary contacts typetype instantaneous 1 NO
control circuit voltage limitsOperational: 0.7...1.30 Uc (at < 50 °C)
Drop-out: 0.1...0.7 Uc (at < 50 °C)
[Ui] rated insulation voltagePower circuit: 600 V conforming to UL 508
Power circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-5-1
Signalling circuit: 600 V conforming to UL 508
Power circuit: 600 V conforming to CSA C22.2 No 14
Signalling circuit: 600 V conforming to CSA C22.2 No 14
[Uimp] rated impulse withstand voltage8 kV
overvoltage categoryIII
mounting supportRail
Plate
flame retardanceV1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
tightening torque1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz
Signalling circuit: ≤ 690 V AC 50/60 Hz
[Ith] conventional free air thermal current20 A (at 50 °C) for power circuit
10 A (at 50 °C) for signalling circuit
Irms rated making capacity110 A AC for power circuit conforming to NF C 63-110
110 A AC for power circuit conforming to IEC 60947
110 A AC for signalling circuit conforming to IEC 60947
rated breaking capacity110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
associated fuse rating25 A gG at ≤ 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660
average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
inrush power in W1.8 W (at 20 °C)
hold-in power consumption in W1.8 W at 20 °C
operating time10...20 ms coil de-energisation and NO opening
30...40 ms coil energisation and NO closing
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability30 Mcycles
maximum operating rate3600 cyc/h
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
insulation resistance> 10 MOhm for signalling circuit
height58 mm
width45 mm
depth57 mm
net weight0.235 kg

Environment

product certificationsUL
CSA
ambient air temperature for operation-25…50 °C
ambient air temperature for storage-50…80 °C
operating altitude2000 m without derating
Questions