Miniature reversing contactor LC2K0601B72

  • Model: 004.014.255
Miniature reversing contactor LC2K0601B72
Manufacturer: Schneider Electric
Barcode: 3389110490688

Main

rangeTeSys
product nameTeSys K
product or component typeReversing contactor
device short nameLC2K
device applicationControl
contactor applicationMotor control
utilisation categoryAC-4
AC-3
device presentationPreassembled with reversing power busbar
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz
Signalling circuit: ≤ 690 V AC 50/60 Hz
[Ie] rated operational current6 A at ≤ 440 V AC AC-3 for power circuit
motor power kW1.5 kW at 220...230 V AC 50/60 Hz
2.2 kW at 380...415 V AC 50/60 Hz
3 kW at 440 V AC 50/60 Hz
3 kW at 480 V AC 50/60 Hz
3 kW at 500...600 V AC 50/60 Hz
3 kW at 660...690 V AC 50/60 Hz
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage24 V AC 50/60 Hz
auxiliary contact composition1 NC
[Uimp] rated impulse withstand voltage8 kV
overvoltage categoryIII
[Ith] conventional free air thermal current20 A (at 50 °C) for power circuit
10 A (at 50 °C) for signalling circuit
Irms rated making capacity110 A AC for power circuit conforming to NF C 63-110
110 A AC for power circuit conforming to IEC 60947
110 A AC for signalling circuit conforming to IEC 60947
rated breaking capacity110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current90 A 50 °C - 1 s for power circuit
85 A 50 °C - 5 s for power circuit
80 A 50 °C - 10 s for power circuit
60 A 50 °C - 30 s for power circuit
45 A 50 °C - 1 min for power circuit
40 A 50 °C - 3 min for power circuit
80 A - 1 s for signalling circuit
90 A - 500 ms for signalling circuit
110 A - 100 ms for signalling circuit
20 A 50 °C - >= 15 min for power circuit
associated fuse rating25 A gG at ≤ 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660
average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 600 V conforming to UL 508
Power circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-5-1
Signalling circuit: 600 V conforming to UL 508
Power circuit: 600 V conforming to CSA C22.2 No 14
Signalling circuit: 600 V conforming to CSA C22.2 No 14
electrical durability1.3 Mcycles 6 A AC-3 at Ue ≤ 440 V
interlocking typeMechanical
mounting supportRail
Plate
standardsNF C 63-110
IEC 60947
VDE 0660
BS 5424
product certificationsCSA
UL
connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solid
Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1.5…4 mm²solid
Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
tightening torque1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
operating time10...20 ms coil energisation and NO closing
10...20 ms coil de-energisation and NO opening
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability5 Mcycles
maximum operating rate3600 cyc/h

Complementary

coil technologyBuilt-in bidirectional peak limiting diode suppressor
control circuit voltage limitsOperational: 0.8...1.15 Uc (at < 50 °C)
Drop-out: 0.2...0.75 Uc (at < 50 °C)
inrush power in VA30 VA (at 20 °C)
hold-in power consumption in VA4.5 VA (at 20 °C)
heat dissipation1.3 W
auxiliary contacts typetype instantaneous 1 NC
signalling circuit frequency≤ 400 Hz
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
non overlap distance0.5 mm
insulation resistance> 10 MOhm for signalling circuit

Environment

IP degree of protectionIP20 conforming to VDE 0106
protective treatmentTC conforming to IEC 60068
TC conforming to DIN 50016
ambient air temperature for operation-25…50 °C
ambient air temperature for storage-50…80 °C
operating altitude2000 m without derating
flame retardanceV1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
height58 mm
width90 mm
depth57 mm
net weight0.39 kg
Questions