Miniature contactor LC1K1201B7

  • Model: 004.014.022
Miniature contactor LC1K1201B7
Manufacturer: Schneider Electric
Barcode: 3389110789621

Main

rangeTeSys
product or component typeContactor
product nameTeSys K
device short nameLC1K
device applicationControl
contactor applicationResistive load
Motor control

Complementary

utilisation categoryAC-4
AC-3
AC-1
poles description3P
power pole contact composition3 NO
[Ie] rated operational current20 A (at < 50 °C) at ≤ 440 V AC AC-1 for power circuit
12 A at ≤ 440 V AC AC-3 for power circuit
16 A (at < 70 °C) at 690 V AC AC-1 for power circuit
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage24 V AC 50/60 Hz
motor power kW4 kW at 480 V AC 50/60 Hz AC-3
4 kW at 500...600 V AC 50/60 Hz AC-3
4 kW at 660...690 V AC 50/60 Hz AC-3
2.2 kW at 400 V AC 50/60 Hz AC-4
3 kW at 220...230 V AC 50/60 Hz AC-3
5.5 kW at 380...415 V AC 50/60 Hz AC-3
5.5 kW at 440 V AC 50/60 Hz AC-3
auxiliary contact composition1 NC
overvoltage categoryIII
[Ith] conventional free air thermal current20 A (at 50 °C) for power circuit
10 A (at 50 °C) for signalling circuit
Irms rated making capacity110 A AC for signalling circuit conforming to IEC 60947
144 A AC for power circuit conforming to NF C 63-110
144 A AC for power circuit conforming to IEC 60947
rated breaking capacity110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
associated fuse rating25 A gG at ≤ 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660
average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
insulation resistance> 10 MOhm for signalling circuit
inrush power in VA30 VA (at 20 °C)
hold-in power consumption in VA4.5 VA (at 20 °C)
heat dissipation1.3 W
control circuit voltage limitsOperational: 0.8...1.15 Uc (at < 50 °C)
Drop-out: 0.2...0.75 Uc (at < 50 °C)
maximum operating rate3600 cyc/h
auxiliary contacts typetype instantaneous 1 NC
signalling circuit frequency≤ 400 Hz
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
operating time10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
non overlap distance0.5 mm
mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6

Environment

product certificationsCSA
UL
protective treatmentTC conforming to IEC 60068
TC conforming to DIN 50016
operating altitude2000 m without derating
flame retardanceV1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102