Contactor PM12-160100 3P, 160A, 4NO+2NC aux.contacts, 400V 50Hz

  • Model: 004.003.271
  • photo 3
  • photo 4
Contactor PM12-160100 400Vac
Manufacturer: TDM
PM12 series AC contactor is mainly used in the circuit of AC 50Hz (60Hz), rated voltage up to 660v, the current up to 16A for long distance making and breaking circuit and it can be formed into electromagnetic starter with thermal relay for protecting circuit from the problem overload. It suits for frequently starting and controlling AC motor.
$110.34
 pcs

Main

[Ue] rated operational voltagePower circuit: <= 660 V AC 50/60 Hz
[Ui] rated insulation voltage
660 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV coil not connected to the power circuit conforming to IEC 60947
Utilisation categoryAC-3
AC-4
Poles description3
Auxiliary contact composition4 NO + 2 NC
[Ie] rated operational current160 A at <= 400 V AC AC-3 for power circuit
Motor power kW75 kW at 380...400 V AC 50/60 Hz (AC-3)
[Uc] control circuit voltage400Vac 50Hz
Control circuit voltage limitsOperational: 0.85...1.1 Uc at 50 Hz (at <55 °C)
Drop-out: 0.2...0.75 Uc at 50 Hz (at <55 °C)
Electrical durability, load AC-3300 000 cycles
Mechanical durability
5 000 000 cycles
Mounting supportPlate

Установочные размеры

PM12-160100 sizes

Электрическая схема

PM12-160100 circuit