Contactor LC1F265

  • Model: 004.007.005
Contactor LC1F265
Manufacturer: Schneider Electric
Barcode: 3389110122459
The F-line contactors offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.
$1,243.73
 pcs

Main

rangeTeSys
product nameTeSys F
product or component typeContactor
device short nameLC1F
contactor applicationResistive load
Motor control
utilisation categoryAC-3
AC-4
AC-1
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltage≤ 1000 V AC 50/60 Hz
≤ 460 V DC
[Ie] rated operational current350 A (at < 40 °C) at ≤ 440 V AC AC-1
265 A (at < 55 °C) at ≤ 440 V AC AC-3
motor power kW132 kW at 380...400 V AC 50/60 Hz (AC-3)
140 kW at 415 V AC 50/60 Hz (AC-3)
140 kW at 440 V AC 50/60 Hz (AC-3)
147 kW at 1000 V AC 50/60 Hz (AC-3)
160 kW at 500 V AC 50/60 Hz (AC-3)
75 kW at 220...240 V AC 50/60 Hz (AC-3)
160 kW at 660...690 V AC 50/60 Hz (AC-3)
51 kW at 400 V AC 50/60 Hz (AC-4)

Complementary

[Uc] control circuit voltage24...1000 V AC 40...400 Hz with LX1/LX9 coil
24...460 V DC with LX4 coil
100...250 V AC 50/60 Hz with LXE coil
100...380 V with LXE coil
[Uimp] rated impulse withstand voltage8 kV
overvoltage categoryIII
[Ith] conventional free air thermal current350 A (at 40 °C)
Irms rated making capacity2650 A AC conforming to IEC 60947-4-1
rated breaking capacity2120 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current2200 A 40 °C - 10 s
1230 A 40 °C - 30 s
950 A 40 °C - 1 min
620 A 40 °C - 3 min
480 A 40 °C - 10 min
associated fuse rating315 A aM at ≤ 440 V
400 A gG at ≤ 440 V
average impedance0.3 mOhm - Ith 350 A 50 Hz
[Ui] rated insulation voltage1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
power dissipation per pole37 W AC-1
21 W AC-3
control circuit voltage limitsOperational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil
Drop-out: 0.35...0.55 Uc AC 40...400 Hz with LX1/LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.15...0.2 Uc DC with LX4 coil
Operational: 85...275 V AC 50/60 Hz with LXE coil
Drop-out: 0...60 V AC 50/60 Hz with LXE coil
Operational: 85...418 V DC with LXE coil
Drop-out: 0...45 V DC with LXE coil
heat dissipation8 W
2.2…2.5 W
operating time40...65 ms closing for with LX1/LX9 coil
100...170 ms opening for with LX1/LX9 coil
40...50 ms closing for with LX4 coil
40...65 ms opening for with LX4 coil
40...80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
mounting supportPlate
standardsIEC 60947-1
IEC 60947-4-1
JIS C8201-4-1
EN 60947-1
EN 60947-4-1
product certificationsABS
CB
DNV
RMRoS
UL
CSA
RINA
LROS (Lloyds register of shipping)
BV
connections - terminalsPower circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm
Power circuit: lugs-ring terminals 1 cable(s) 240 mm²
Power circuit: connector 1 cable(s) 240 mm²
Power circuit: bolted connection
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end
tightening torquePower circuit: 35 N.m
Control circuit: 1.2 N.m
Control circuit: 0.6 N.m
mechanical durability10 Mcycles
inrush power in VA600…700 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
655…803 VA (at 20 °C)with LX4 coil
300…350 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
300…310 VA (at 20 °C)with LXE coil
hold-in power consumption in VA8…10 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
3.68…4.53 VA (at 20 °C)with LX4 coil
4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
2.5…4.0 VA (at 20 °C)with LXE coil
maximum operating rate2400 cyc/h 55 °C
compatibility codeLC1F

Environment

IP degree of protectionIP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
protective treatmentTH
ambient air temperature for operation-5…55 °C
ambient air temperature for storage-60…80 °C
permissible ambient air temperature around the device-40…70 °C
mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 5 Gn, 5...300 Hz
Shocks contactor open: 6 Gn for 1/2 sine wave (11 ms)
Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)
height203 mm
width201.5 mm
depth213 mm
net weight8.54 kg

Dimensions

Dimension LC1F265