TeSys D series contactor LC1D80P7

  • Model: 004.001.089
Contactor LC1D80P7
Manufacturer: Schneider Electric
Barcode: 3389110442823
Control circuit voltage 230VAC 50/60Hz.
Rated operational current 80 A (АС-3).
Auxiliary contact composition 1 NO + 1 NC.
Price by call

Main

rangeTeSys
product nameTeSys D
product or component typeContactor
device short nameLC1D
contactor applicationResistive load
Motor control
utilisation categoryAC-4
AC-3
AC-1
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: ≤ 300 V DC 25...400 Hz
Power circuit: ≤ 690 V AC
[Ie] rated operational current125 A (at < 60 °C) at ≤ 440 V AC AC-1 for power circuit
80 A (at < 60 °C) at ≤ 440 V AC AC-3 for power circuit
motor power kW22 kW at 220...230 V AC 50/60 Hz (AC-3)
37 kW at 380...400 V AC 50/60 Hz (AC-3)
45 kW at 415...440 V AC 50/60 Hz (AC-3)
55 kW at 500 V AC 50/60 Hz (AC-3)
45 kW at 660...690 V AC 50/60 Hz (AC-3)
45 kW at 1000 V AC 50/60 Hz (AC-3)
15 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
7.5 hp at 115 V AC 50/60 Hz for 1 phase motors
15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
25 hp at 230/240 V AC 50/60 Hz for 3 phases motors
60 hp at 460/480 V AC 50/60 Hz for 3 phases motors
60 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage230 V AC 50/60 Hz
auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947
overvoltage categoryIII
[Ith] conventional free air thermal current10 A (at 60 °C) for signalling circuit
125 A (at 60 °C) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1100 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current640 A 40 °C - 10 s for power circuit
990 A 40 °C - 1 s for power circuit
135 A 40 °C - 10 min for power circuit
320 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
200 A gG at ≤ 690 V coordination type 1 for power circuit
160 A gG at ≤ 690 V coordination type 2 for power circuit
average impedance0.8 mOhm - Ith 125 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability0.8 Mcycles 125 A AC-1 at Ue ≤ 440 V
1.5 Mcycles 80 A AC-3 at Ue ≤ 440 V
power dissipation per pole5.1 W AC-3
12.5 W AC-1
Front coverWith
mounting supportRail
Plate
standardsCSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certificationsDNV
LROS (Lloyds register of shipping)
GOST
CCC
GL
RINA
BV
CSA
UL
connections - terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible without cable end
Power circuit: connector 2 cable(s) 4…25 mm²flexible without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible with cable end
Power circuit: connector 2 cable(s) 4…16 mm²flexible with cable end
Power circuit: connector 1 cable(s) 4…50 mm²solid without cable end
Power circuit: connector 2 cable(s) 4…25 mm²solid without cable end
tightening torqueControl circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
Power circuit: 12 N.m - on connector hexagonal screw head 4 mm
operating time20...35 ms closing
6...20 ms opening
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability4 Mcycles
maximum operating rate3600 cyc/h 60 °C

Complementary

coil technologyWithout built-in suppressor module
control circuit voltage limits0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz
1...1.1 Uc (55…70 °C):operational AC 50/60 Hz
inrush power in VA245 VA 60 Hz cos phi 0.75 (at 20 °C)
245 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA26 VA 60 Hz cos phi 0.3 (at 20 °C)
26 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation6…10 W at 50/60 Hz
auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency25...400 Hz
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
non-overlap time1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance> 10 MOhm for signalling circuit

Environment

IP degree of protectionIP20 front face conforming to IEC 60529
protective treatmentTH conforming to IEC 60068-2-30
pollution degree3
ambient air temperature for operation-40…60 °C
60…70 °C with derating
ambient air temperature for storage-60…80 °C
operating altitude0...3000 m
fire resistance850 °C conforming to IEC 60695-2-1
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz
Shocks contactor open: 8 Gn for 11 ms
Vibrations contactor closed: 3 Gn, 5...300 Hz
Shocks contactor closed: 10 Gn for 11 ms
height127 mm
width85 mm
depth130 mm
net weight1.59 kg

Dimensions and internal circuit

Dimension LC1D80P7   circuit of LC1D80P7

3-pole contactors LC1D with coil 230Vac 50/60Hz

Model Rated operational voltage AC-3 (Ue ≤ 400V), A Standard power ratings of 3-phase motors 50-60 Hz in category AC-3 (t≤60°C), kW
220V/230V 380V/400V 415V 440V 500V 660V/690V 1000V
LC1D09P7 9 2,2 4 4 4 5,5 5,5 -
LC1D12P7 12 3 5,5 5,5 5,5 7,5 7,5 -
LC1D18P7 18 4 7,5 9 9 10 10 -
LC1D25P7 25 5,5 11 11 11 15 15 -
LC1D32P7 32 7,5 15 15 15 18,5 18,5 -
LC1D38P7 38 9 18,5 18,5 18,5 18,5 18,5 -
LC1D40AP7 40 11 18,5 22 22 22 30 22
LC1D50AP7 50 15 22 25 30 30 33 30
LC1D65AP7 65 18,5 30 37 37 37 37 37
LC1D80P7 80 22 37 45 45 55 45 45
LC1D95P7 95 25 45 45 45 55 45 45
LC1D115P7 115 30 55 59 59 75 80 75
LC1D150P7 150 40 75 80 80 90 100 90

Standard control circuit voltages on 42Vac 50/60Hz

a.c. supply
Voltage, V 24 42 48 110 115 220 230 240 380 400 415 440 500
LC1-D09..D150 (D115 and D150 coils with integral suppression device fitted as standard)
50/60Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 -
LC1-D40...D115
50Hz B5 D5 E5 F5 FE5 M5 P5 U5 Q5 V5 N5 R5 S5
60Hz B6 - E6 F6 - M6 - U6 Q6 - - R6 -
d.c. supply
Voltage, V 12 24 36 48 60 72 110 125 220 250 440
LC1-D09...D38 (coils with integral suppression device fitted as standard)
U 0,7…1,25 Uc JD BD CD ED ND SD FD GD MD UD RD
LC1-D40...D95
U 0,85…1,1 Uc JD BD CD ED ND SD FD GD MD UD RD
U 0,75…1,2 Uc JW BW CW EW - SW FW - MW - -
LC1-D115 and D150 (coils with integral suppression device fitted as standard)
U 0,75…1,2 Uc - BD - ED ND SD FD GD MD UD RD
Low consumption
Volatage DC 5 12 20 24 48 110 220 250
LC1-D09..D38 (coils with integral suppression device fitted as standard)
U 0,7...1,25 Uc AL JL ZL BL EL FL ML UL
Questions
WhatsAppTelegramViberVKemail