TeSys D series contactor LC1D80E7

  • Model: 004.001.102
Contactor LC1D80E7
Manufacturer: Schneider Electric
Barcode: 3389110440522
Control circuit voltage 48VAC 50/60Hz.
Rated operational current 80 A (АС-3).
Auxiliary contact composition 1 NO + 1 NC.
Price by call

Main

range TeSys
product name TeSys D
product or component type Contactor
device short name LC1D
contactor application Motor control
Resistive load
utilisation category AC-3
AC-1
AC-4
poles description 3P
power pole contact composition 3 NO
[Ue] rated operational voltage Power circuit: ≤ 300 V DC 25...400 Hz
Power circuit: ≤ 690 V AC
[Ie] rated operational current 125 A (at < 60 °C) at ≤ 440 V AC AC-1 for power circuit
80 A (at < 60 °C) at ≤ 440 V AC AC-3 for power circuit
motor power kW 22 kW at 220...230 V AC 50/60 Hz (AC-3)
37 kW at 380...400 V AC 50/60 Hz (AC-3)
45 kW at 415...440 V AC 50/60 Hz (AC-3)
55 kW at 500 V AC 50/60 Hz (AC-3)
45 kW at 660...690 V AC 50/60 Hz (AC-3)
45 kW at 1000 V AC 50/60 Hz (AC-3)
15 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA) 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
7.5 hp at 115 V AC 50/60 Hz for 1 phase motors
15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
25 hp at 230/240 V AC 50/60 Hz for 3 phases motors
60 hp at 460/480 V AC 50/60 Hz for 3 phases motors
60 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit type AC at 50/60 Hz
[Uc] control circuit voltage 48 V AC 50/60 Hz
auxiliary contact composition 1 NO + 1 NC
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947
overvoltage category III
[Ith] conventional free air thermal current 10 A (at 60 °C) for signalling circuit
125 A (at 60 °C) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1100 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 640 A 40 °C - 10 s for power circuit
990 A 40 °C - 1 s for power circuit
135 A 40 °C - 10 min for power circuit
320 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
200 A gG at ≤ 690 V coordination type 1 for power circuit
160 A gG at ≤ 690 V coordination type 2 for power circuit
average impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit
[Ui] rated insulation voltage Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability 0.8 Mcycles 125 A AC-1 at Ue ≤ 440 V
1.5 Mcycles 80 A AC-3 at Ue ≤ 440 V
power dissipation per pole 5.1 W AC-3
12.5 W AC-1
Front cover With
mounting support Plate
Rail
standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications CSA
BV
UL
GOST
RINA
CCC
GL
LROS (Lloyds register of shipping)
DNV
connections - terminals Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible without cable end
Power circuit: connector 2 cable(s) 4…25 mm²flexible without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible with cable end
Power circuit: connector 2 cable(s) 4…16 mm²flexible with cable end
Power circuit: connector 1 cable(s) 4…50 mm²solid without cable end
Power circuit: connector 2 cable(s) 4…25 mm²solid without cable end
tightening torque Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
Power circuit: 12 N.m - on connector hexagonal screw head 4 mm
operating time 20...35 ms closing
6...20 ms opening
safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability 4 Mcycles
maximum operating rate 3600 cyc/h 60 °C

Complementary

coil technology Without built-in suppressor module
control circuit voltage limits 0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz
1...1.1 Uc (55…70 °C):operational AC 50/60 Hz
inrush power in VA 245 VA 60 Hz cos phi 0.75 (at 20 °C)
245 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA 26 VA 60 Hz cos phi 0.3 (at 20 °C)
26 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation 6…10 W at 50/60 Hz
auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency 25...400 Hz
minimum switching current 5 mA for signalling circuit
minimum switching voltage 17 V for signalling circuit
non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance > 10 MOhm for signalling circuit
contact compatibility M11
compatibility code LC1D
motor power range 55…100 kW at 480…500 V 3 phases
15…25 kW at 200…240 V 3 phases
30…50 kW at 380…440 V 3 phases
30…50 kW at 480…500 V 3 phases
motor starter type Direct on-line contactor
contactor coil voltage 48 V AC standard

Environment

IP degree of protection IP20 front face conforming to IEC 60529
protective treatment TH conforming to IEC 60068-2-30
pollution degree 3
ambient air temperature for operation -40…60 °C
60…70 °C with derating
ambient air temperature for storage -60…80 °C
operating altitude 0...3000 m
fire resistance 850 °C conforming to IEC 60695-2-1
flame retardance V1 conforming to UL 94
mechanical robustness Vibrations contactor open: 2 Gn, 5...300 Hz
Shocks contactor open: 8 Gn for 11 ms
Vibrations contactor closed: 3 Gn, 5...300 Hz
Shocks contactor closed: 10 Gn for 11 ms
height 127 mm
width 85 mm
depth 130 mm
net weight 1.59 kg

Dimensions and internal circuit

Dimension LC1D80E7
circuit of LC1D80E7

3-pole contactors LC1D with coil 48Vac 50/60Hz

Model Rated operational voltage AC-3 (Ue ≤ 400V), A Standard power ratings of 3-phase motors 50-60 Hz in category AC-3 (t≤60°C), kW
220V/230V 380V/400V 415V 440V 500V 660V/690V 1000V
LC1D09E7 9 2,2 4 4 4 5,5 5,5 -
LC1D12E7 12 3 5,5 5,5 5,5 7,5 7,5 -
LC1D18E7 18 4 7,5 9 9 10 10 -
LC1D25E7 25 5,5 11 11 11 15 15 -
LC1D32E7 32 7,5 15 15 15 18,5 18,5 -
LC1D38E7 38 9 18,5 18,5 18,5 18,5 18,5 -
LC1D40AE7 40 11 18,5 22 22 22 30 22
LC1D50AE7 50 15 22 25 30 30 33 30
LC1D65AE7 65 18,5 30 37 37 37 37 37
LC1D80E7 80 22 37 45 45 55 45 45
LC1D95E7 95 25 45 45 45 55 45 45
LC1D115E7 115 30 55 59 59 75 80 75
LC1D150E7 150 40 75 80 80 90 100 90

Standard control circuit voltages on 42Vac 50/60Hz

a.c. supply
Voltage, V 24 42 48 110 115 220 230 240 380 400 415 440 500
LC1-D09..D150 (D115 and D150 coils with integral suppression device fitted as standard)
50/60Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 -
LC1-D40...D115
50Hz B5 D5 E5 F5 FE5 M5 P5 U5 Q5 V5 N5 R5 S5
60Hz B6 - E6 F6 - M6 - U6 Q6 - - R6 -
d.c. supply
Voltage, V 12 24 36 48 60 72 110 125 220 250 440
LC1-D09...D38 (coils with integral suppression device fitted as standard)
U 0,7…1,25 Uc JD BD CD ED ND SD FD GD MD UD RD
LC1-D40...D95
U 0,85…1,1 Uc JD BD CD ED ND SD FD GD MD UD RD
U 0,75…1,2 Uc JW BW CW EW - SW FW - MW - -
LC1-D115 and D150 (coils with integral suppression device fitted as standard)
U 0,75…1,2 Uc - BD - ED ND SD FD GD MD UD RD
Low consumption
Volatage DC 5 12 20 24 48 110 220 250
LC1-D09..D38 (coils with integral suppression device fitted as standard)
U 0,7...1,25 Uc AL JL ZL BL EL FL ML UL
Questions