Contactor LC1D50AB7

  • Model: 004.001.035
Contactor LC1D50AB7
Manufacturer: Schneider Electric
Barcode: 3389119408622
Contactor LC1D50AB7 is mainly used in the circuit of AC 50Hz (60Hz), rated voltage up to 660v, the current up to 50A for long distance making and breaking circuit and it can be formed into electromagnetic starter with thermal relay for protecting circuit from the problem overload.
Coil voltage is 24Vac 50/60Hz.

Main

rangeTeSys
product nameTeSys D
product or component typeContactor
device short nameLC1D
contactor applicationResistive load
Motor control
utilisation categoryAC-1
AC-4
AC-3
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: ≤ 690 V AC 25...400 Hz
Power circuit: ≤ 300 V DC
[Ie] rated operational current50 A (at < 60 °C) at ≤ 440 V AC AC-3 for power circuit
80 A (at < 60 °C) at ≤ 440 V AC AC-1 for power circuit
motor power kW15 kW at 220...230 V AC 50/60 Hz (AC-3)
22 kW at 380...400 V AC 50/60 Hz (AC-3)
30 kW at 500 V AC 50/60 Hz (AC-3)
33 kW at 660...690 V AC 50/60 Hz (AC-3)
25 kW at 415 V AC 50/60 Hz (AC-3)
30 kW at 440 V AC 50/60 Hz (AC-3)
11 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)3 hp at 115 V AC 50/60 Hz for 1 phase motors
7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
15 hp at 200/208 V AC 50/60 Hz for 3 phases motors
15 hp at 230/240 V AC 50/60 Hz for 3 phases motors
40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
40 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage24 V AC 50/60 Hz
auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
overvoltage categoryIII
[Ith] conventional free air thermal current10 A (at 60 °C) for signalling circuit
80 A (at 60 °C) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
900 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity900 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current400 A 40 °C - 10 s for power circuit
810 A 40 °C - 1 s for power circuit
84 A 40 °C - 10 min for power circuit
208 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
100 A gG at ≤ 690 V coordination type 1 for power circuit
100 A gG at ≤ 690 V coordination type 2 for power circuit
average impedance1.5 mOhm - Ith 80 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
electrical durability1.45 Mcycles 50 A AC-3 at Ue ≤ 440 V
1.1 Mcycles 80 A AC-1 at Ue ≤ 440 V
power dissipation per pole3.7 W AC-3
9.6 W AC-1
Front coverWith
mounting supportPlate
Rail
standardsCSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certificationsDNV
LROS (Lloyds register of shipping)
CCC
GOST
BV
RINA
CSA
UL
GL
connections - terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: screw connection 1 cable(s) 1…35 mm²flexible without cable end
Power circuit: screw connection 2 cable(s) 1…25 mm²flexible without cable end
Power circuit: screw connection 1 cable(s) 1…35 mm²flexible with cable end
Power circuit: screw connection 2 cable(s) 1…25 mm²flexible with cable end
Power circuit: screw connection 1 cable(s) 1…35 mm²solid without cable end
Power circuit: screw connection 2 cable(s) 1…25 mm²solid without cable end
tightening torqueControl circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm² hexagonal screw head 4 mm
Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² hexagonal screw head 4 mm
operating time4...19 ms opening
12...26 ms closing
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability6 Mcycles
maximum operating rate3600 cyc/h 60 °C

Complementary

coil technologyWithout built-in suppressor module
control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
inrush power in VA140 VA 60 Hz cos phi 0.75 (at 20 °C)
160 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA13 VA 60 Hz cos phi 0.3 (at 20 °C)
15 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation4…5 W at 50/60 Hz
auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency25...400 Hz
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
non-overlap time1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance> 10 MOhm for signalling circuit

Environment

IP degree of protectionIP20 front face conforming to IEC 60529
protective treatmentTH conforming to IEC 60068-2-30
pollution degree3
ambient air temperature for operation-40…60 °C
60…70 °C with derating
ambient air temperature for storage-60…80 °C
operating altitude0...3000 m
fire resistance850 °C conforming to IEC 60695-2-1
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 10 Gn for 11 ms
height122 mm
width55 mm
depth120 mm
net weight0.855 kg