Contactor LC1D32M7

  • Model: 004.001.045
Contactor LC1D32M7
Manufacturer: Schneider Electric
Barcode: 3389110351088
Contactor LC1D32M7 is mainly used in the circuit of AC 50Hz (60Hz), rated voltage up to 660v, the current up to 32A for long distance making and breaking circuit and it can be formed into electromagnetic starter with thermal relay for protecting circuit from the problem overload.
Price by call

Main

rangeTeSys
product nameTeSys D
product or component typeContactor
device short nameLC1D
contactor applicationResistive load
Motor control
utilisation categoryAC-4
AC-1
AC-3
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: ≤ 690 V AC 25...400 Hz
Power circuit: ≤ 300 V DC
[Ie] rated operational current32 A (at < 60 °C) at ≤ 440 V AC AC-3 for power circuit
50 A (at < 60 °C) at ≤ 440 V AC AC-1 for power circuit
motor power kW7.5 kW at 220...230 V AC 50/60 Hz (AC-3)
15 kW at 380...400 V AC 50/60 Hz (AC-3)
15 kW at 415...440 V AC 50/60 Hz (AC-3)
18.5 kW at 500 V AC 50/60 Hz (AC-3)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3)
7.5 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)2 hp at 115 V AC 50/60 Hz for 1 phase motors
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
20 hp at 460/480 V AC 50/60 Hz for 3 phases motors
30 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage220 V AC 50/60 Hz
auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
overvoltage categoryIII
[Ith] conventional free air thermal current10 A (at 60 °C) for signalling circuit
50 A (at 60 °C) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity550 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current260 A 40 °C - 10 s for power circuit
430 A 40 °C - 1 s for power circuit
60 A 40 °C - 10 min for power circuit
138 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at ≤ 690 V coordination type 1 for power circuit
63 A gG at ≤ 690 V coordination type 2 for power circuit
average impedance2 mOhm - Ith 50 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability1.65 Mcycles 32 A AC-3 at Ue ≤ 440 V
1.4 Mcycles 50 A AC-1 at Ue ≤ 440 V
power dissipation per pole2 W AC-3
5 W AC-1
Front coverWith
mounting supportPlate
Rail
standardsCSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certificationsDNV
RINA
LROS (Lloyds register of shipping)
CCC
CSA
GL
GOST
BV
UL
connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid without cable end
tightening torqueControl circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
operating time12...22 ms closing
4...19 ms opening
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability15 Mcycles
maximum operating rate3600 cyc/h 60 °C

Complementary

coil technologyWithout built-in suppressor module
control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
inrush power in VA70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation2…3 W at 50/60 Hz
auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency25...400 Hz
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
non-overlap time1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance> 10 MOhm for signalling circuit

Environment

IP degree of protectionIP20 front face conforming to IEC 60529
protective treatmentTH conforming to IEC 60068-2-30
pollution degree3
ambient air temperature for operation-40…60 °C
60…70 °C with derating
ambient air temperature for storage-60…80 °C
operating altitude0...3000 m
fire resistance850 °C conforming to IEC 60695-2-1
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 8 Gn for 11 ms
height85 mm
width45 mm
depth92 mm
net weight0.375 kg

Dimensions and internal circuit

Dimension LC1D32M7
circuit of LC1D32M7width="145" />