Contactor LC1D150F7

  • Model: 004.001.079
  • photo 3
  • photo 4
Contactor LC1D150F7
Manufacturer: Schneider Electric
Contactor LC1D150F7 is mainly used in the circuit of AC 50Hz (60Hz), rated voltage up to 660v, the current up to 150A for long distance making and breaking circuit and it can be formed into electromagnetic starter with thermal relay for protecting circuit from the problem overload.
Rated current - 150A (AC-3),
Rated coil voltage - 110V 50/60Hz.

Main

rangeTeSys
product nameTeSys D
product or component typeContactor
device short nameLC1D
contactor applicationMotor control
Resistive load
utilisation categoryAC-4
AC-3
AC-1
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: ≤ 1000 V AC 25...400 Hz
Power circuit: ≤ 300 V DC
[Ie] rated operational current200 A (at < 60 °C) at ≤ 440 V AC AC-1 for power circuit
150 A (at < 60 °C) at ≤ 440 V AC AC-3 for power circuit
motor power kW40 kW at 220...230 V AC 50/60 Hz (AC-3)
75 kW at 380...400 V AC 50/60 Hz (AC-3)
80 kW at 415...440 V AC 50/60 Hz (AC-3)
90 kW at 500 V AC 50/60 Hz (AC-3)
100 kW at 660...690 V AC 50/60 Hz (AC-3)
75 kW at 1000 V AC 50/60 Hz (AC-3)
22 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)40 hp at 200/208 V AC 50/60 Hz for 3 phases motors
50 hp at 230/240 V AC 50/60 Hz for 3 phases motors
100 hp at 460/480 V AC 50/60 Hz for 3 phases motors
125 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage110 V AC 50/60 Hz
auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947
overvoltage categoryIII
[Ith] conventional free air thermal current200 A (at 60 °C) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1660 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity1400 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current250 A 40 °C - 10 min for power circuit
580 A 40 °C - 1 min for power circuit
1200 A 40 °C - 10 s for power circuit
1400 A 40 °C - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
315 A gG at ≤ 690 V coordination type 1 for power circuit
250 A gG at ≤ 690 V coordination type 2 for power circuit
average impedance0.6 mOhm - Ith 200 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability0.85 Mcycles 150 A AC-3 at Ue ≤ 440 V
1 Mcycles 200 A AC-1 at Ue ≤ 440 V
power dissipation per pole24 W AC-1
13.5 W AC-3
Front coverWith
mounting supportPlate
Rail
standardsCSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certificationsCCC
GOST
DNV
UL
LROS (Lloyds register of shipping)
BV
GL
RINA
CSA
connections - terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Power circuit: connector 1 cable(s) 10…120 mm²flexible without cable end
Power circuit: connector 2 cable(s) 10…50 mm²flexible without cable end
Power circuit: connector 1 cable(s) 10…120 mm²flexible with cable end
Power circuit: connector 2 cable(s) 10…50 mm²flexible with cable end
Power circuit: connector 1 cable(s) 10…120 mm²solid without cable end
Power circuit: connector 2 cable(s) 10…50 mm²solid without cable end
tightening torqueControl circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 12 N.m - on connector hexagonal screw head 4 mm
operating time20...35 ms closing
40...75 ms opening
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability8 Mcycles
maximum operating rate1200 cyc/h 60 °C

Complementary

coil technologyBuilt-in bidirectional peak limiting diode suppressor
control circuit voltage limits0.3...0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.15 Uc (-40…55 °C):operational AC 50/60 Hz
1...1.15 Uc (55…70 °C):operational AC 50/60 Hz
inrush power in VA280…350 VA 60 Hz cos phi 0.9 (at 20 °C)
280…350 VA 50 Hz cos phi 0.9 (at 20 °C)
hold-in power consumption in VA2…18 VA 60 Hz cos phi 0.9 (at 20 °C)
2…18 VA 50 Hz cos phi 0.9 (at 20 °C)
heat dissipation3…4.5 W at 50/60 Hz
auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency25...400 Hz
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
non-overlap time1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance> 10 MOhm for signalling circuit

Environment

IP degree of protectionIP20 front face conforming to IEC 60529
protective treatmentTH conforming to IEC 60068-2-30
pollution degree3
ambient air temperature for operation-40…60 °C
60…70 °C with derating
ambient air temperature for storage-60…80 °C
operating altitude0...3000 m
fire resistance850 °C conforming to IEC 60695-2-1
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 6 Gn for 11 ms
height158 mm
width120 mm
depth136 mm
net weight2.5 kg

Dimensions and internal circuit

Dimension LC1D150F7   circuit of LC1D150F7

Auxiliaries and accessories for LC1D150F7

background
LA9D11502
 
 
Questions
WhatsAppTelegramViberVKemail