The B-line contactors offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.

Main

rangeTeSys
product nameTeSys B
product or component typeContactor
device short nameLC1BP
contactor applicationMotor-heating-lighting
utilisation categoryAC-1
AC-3
control circuit typeAC
coil typeStandard
poles description3P
pole contact composition3 NO
[Ie] rated operational current2000 A (at < 40 °C) AC AC-1 for power circuit
1500 A (at < 55 °C) AC AC-3 for power circuit
motor power kW425 kW at 220...230 V AC 50/60 Hz
670 kW at 1000 V AC 50/60 Hz
700 kW at 500 V AC 50/60 Hz
750 kW at 380...400 V AC 50/60 Hz
750 kW at 660...690 V AC 50/60 Hz
800 kW at 415 V AC 50/60 Hz
800 kW at 440 V AC 50/60 Hz
auxiliary contact composition3 NO + 1 NC
[Uc] control circuit voltage220 V AC 50...400 Hz

Complementary

control circuit voltage limitsOperational: 0.85...1.1 Uc at 50...400 Hz
Drop-out: 0.35...0.5 Uc at 50...400 Hz
[Ui] rated insulation voltage1000 V - for power circuit conforming to IEC 60158-1
1000 V - for power circuit conforming to IEC 60947-4
1500 V - for power circuit conforming to VDE 0110 group C
mounting modeFixed
mounting supportBar support bracket
Notched mounting rails
connections - terminalsPower circuit: bars 3 x - busbar cross section: 100 x 5 mm
tightening torquePower circuit: 35 N.m - on bars
[Ue] rated operational voltagePower circuit: ≤ 1000 V AC 50/60 Hz
[Ith] conventional free air thermal current2000 A (at 40 °C) for power circuit
Irms rated making capacity15000 A at 1000 V AC for power circuit conforming to IEC 60158-1
15000 A at 1000 V AC for power circuit conforming to IEC 60947-4
rated breaking capacity12000 A at 500 V for power circuit conforming to IEC 60158-1
12000 A at 500 V for power circuit conforming to IEC 60947-4
15000 A at 440 V for power circuit conforming to IEC 60158-1
15000 A at 440 V for power circuit conforming to IEC 60947-4
5000 A at 1000 V for power circuit conforming to IEC 60158-1
5000 A at 1000 V for power circuit conforming to IEC 60947-4
9000 A at 660...690 V for power circuit conforming to IEC 60158-1
9000 A at 660...690 V for power circuit conforming to IEC 60947-4
associated fuse rating1600 A aM at ≤ 440 V for power circuit
2000 A gI at ≤ 440 V for power circuit
average impedance0.13 mOhm - Ith 2000 A 50 Hz for power circuit
power dissipation per pole290 W AC-3 - Ith 2000 A
520 W AC-1 - Ith 2000 A
inrush power in VA1300 VA
hold-in power consumption in VA31 VA 50/60 Hz
operating time100...150 ms closing
50...100 ms opening
mechanical durability1200000 cycles
maximum operating rate120 cyc/h 55 °C
height490 mm
width790 mm
depth475 mm
net weight94 kg

Environment

standardsBS 5424
IEC 60947-4
NF C 63-110
IEC 60158-1
VDE 0660
product certificationsCSA
BV
RINA
protective treatmentTC
TH
ambient air temperature for operation-5…55 °C
ambient air temperature for storage-60…80 °C
operating altitude3000 m without derating