Contactor LC1-D1201-220VAC

  • Model: 004.001.003
Contactor LC1-D1201-220VAC
LC1-D series AC contactor is mainly used in the circuit of AC 50Hz (60Hz), rated voltage up to 660v, the current up to 12A for long distance making and breaking circuit and it can be formed into electromagnetic starter with thermal relay for protecting circuit from the problem overload. It suits for frequently starting and controlling AC motor.

Main

[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Ui] rated insulation voltage
660 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV coil not connected to the power circuit conforming to IEC 60947
Utilisation categoryAC-3
AC-1
Poles description3
Auxiliary contact composition1 NC
[Ie] rated operational current12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
25 A (at <60 °C) at <= 415 V AC AC-1 for power circuit
Motor power kW5,5 kW at 380...400 V AC 50/60 Hz (AC-3)
[Uc] control circuit voltage220...230Vac 50Hz
220...240Vac 60Hz
Control circuit voltage limitsOperational: 0.85...1.1 Uc at 50 Hz (at <55 °C)
Drop-out: 0.3...0.6 Uc at 50 Hz (at <55 °C)
Electrical durability, load AC-31 000 000 cycles
Mechanical durability
10 000 000 cycles
Mounting supportPlate
DIN rail

Dimensions and internal circuit

LC1-D1201 contactor size LC1-D1201 circuit

Auxiliaries and accessories for LC1-D1201-220VAC

background

 
 
background

 
 

Similar or replacement products LC1-D1201-220VAC

background
LC1E1201M5
 
 