Contactor LC1E95Q5

  • Model: 004.005.124
Contactor LC1E95Q5
Manufacturer: Schneider Electric
Barcode: 3606480339448
Electromechanical contactor LC1E95Q5 95A 400V AC3 380V 50Hz used for power management and protection:
 - loads on AC power with a coefficient ≥0.95 (incandescent lamps, heating elements, etc.) - the category of use AC-1. Rated current - 120 Amps.
 - asynchronous squirrel-cage motors - the category of use AC-3. Rated Current - 95 Amps.
Voltage control coil - 380V~ 50Hz.

Main

rangeEasyPact
product nameEasyPact TVS
product or component typeContactor
device short nameLC1E
contactor applicationResistive load
Motor control
utilisation categoryAC-1
AC-3
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: ≤ 690 V AC 50/60 Hz
[Ie] rated operational current95 A (at < 60 °C) at ≤ 440 V AC AC-3 for power circuit
125 A (at < 60 °C) at ≤ 440 V AC AC-1 for power circuit
motor power kW45 kW at 415 V
45 kW at 440 V
45 kW at 500 V
25 kW at 220...230 V AC 50/60 Hz
45 kW at 380...400 V
55 kW at 660...690 V
control circuit typeAC at 50 Hz
[Uc] control circuit voltage380 V AC 50 Hz
height127 mm
width85 mm
depth121 mm
net weight1.52 kg
colourGrey (RAL 7011)

Complementary

auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV coil not connected to the power circuit conforming to IEC 60947
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
overvoltage categoryIII
Irms rated making capacity950 A at 440 V AC for power circuit conforming to IEC 60947-4-1
rated breaking capacity760 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current135 A 40 °C - 600 s for power circuit
800 A 40 °C - 10 s for power circuit
400 A 40 °C - 60 s for power circuit
associated fuse rating10 A gG at ≤ 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
160 A gG at ≤ 690 V coordination type 1 for power circuit
average impedance0.8 mOhm - Ith 120 A 50 Hz for power circuit
power dissipation per pole7.2 W AC-3
12 W AC-1
control circuit voltage limitsOperational: 0.85...1.1 Uc at 50 Hz (at < 55 °C)
Drop-out: 0.3...0.6 Uc at 50 Hz (at < 55 °C)
operating time20...35 ms on closing
6...30 ms on opening
mechanical durability300000 cycles
maximum operating rate1200 cyc/h 60 °C
inrush power in VA200 VA 50 Hz cos phi 0.75 (at 20 °C)
220 VA 60 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA22 VA 60 Hz cos phi 0.3 (at 20 °C)
20 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation6…10 W for control circuit
minimum switching current5 mA for control circuit
minimum switching voltage17 V for control circuit
non-overlap time1.5 ms on energisation guaranteed between NC and NO contact
1.5 ms on de-energisation guaranteed between NC and NO contact
insulation resistance> 10 MOhm for control circuit
electrical durability350000 cycles AC-3
900000 cycles AC-1
mounting supportPlate
DIN rail
connections - terminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 4…50 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 4…16 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 4…50 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 4…50 mm² - cable stiffness: solid without cable end
Recommended tightening torqueControl circuit: 1.2 N.m
Power circuit: 12 N.m
Max tightening torqueControl circuit: 1.4 N.m
Power circuit: 13.5 N.m

Environment

standardsIEC 60947-5-1
IEC 60947-4-1
IEC 60947-1
product certificationsEAC
CE
IP degree of protectionIP2x conforming to IEC 60529
protective treatmentTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
pollution degree3
ambient air temperature for operation-5…55 °C
ambient air temperature for storage-60…80 °C
permissible ambient air temperature around the device-20…70 °C at Uc
operating altitude3000 m without derating
fire resistance850 °C conforming to IEC 60695-2-1
mechanical robustnessVibrations contactor open: 1.5 Gn, 5...300 Hz
Vibrations contactor closed: 3 Gn, 5...300 Hz
Shocks contactor open: 6 Gn for 11 ms
Shocks contactor closed: 7 Gn for 11 ms

Dimensions and internal circuit

Sizes of LC1E95Q5 LC1-E095 circuit

Auxiliaries and accessories for LC1E95Q5

background
LAEM4
 
 
Questions
WhatsAppTelegramViberVKemail