Contactor LC1E2501N5

  • Model: 004.005.135
Contactor LC1E2501N5
Manufacturer: Schneider Electric
Barcode: 3606480361500
The E-line contactors LC1E2501N5 1NC 25A 400V AC3 415V/50Hz offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.

Main

rangeEasyPact
product nameEasyPact TVS
product or component typeContactor
device short nameLC1E
contactor applicationMotor control
Resistive load
utilisation categoryAC-3
AC-1
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: ≤ 690 V AC 50/60 Hz
[Ie] rated operational current25 A (at < 60 °C) at ≤ 440 V AC AC-3 for power circuit
36 A (at < 60 °C) at ≤ 440 V AC AC-1 for power circuit
motor power kW5.5 kW at 220...230 V AC 50/60 Hz
11 kW at 380...400 V
11 kW at 415 V
11 kW at 440 V
15 kW at 500 V
15 kW at 660...690 V
control circuit typeAC at 50 Hz
[Uc] control circuit voltage415 V AC 50 Hz
height74 mm
width45 mm
depth85 mm
net weight0.36 kg
colourGrey (RAL 7011)

Complementary

auxiliary contact composition1 NC
[Uimp] rated impulse withstand voltage6 kV coil not connected to the power circuit conforming to IEC 60947
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
overvoltage categoryIII
[Ith] conventional free air thermal current36 A (at 55 °C)
Irms rated making capacity250 A at 440 V AC for power circuit conforming to IEC 60947-4-1
rated breaking capacity200 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current240 A 40 °C - 10 s for power circuit
120 A 40 °C - 60 s for power circuit
50 A 40 °C - 600 s for power circuit
associated fuse rating10 A gG at ≤ 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
40 A gG at ≤ 690 V coordination type 1 for power circuit
average impedance2.5 mOhm - Ith 36 A 50 Hz for power circuit
power dissipation per pole1.6 W AC-1
2.5 W AC-3
control circuit voltage limitsOperational: 0.85...1.1 Uc at 50 Hz (at < 55 °C)
Drop-out: 0.3...0.6 Uc at 50 Hz (at < 55 °C)
operating time12...22 ms on closing
4...19 ms on opening
mechanical durability1000000 cycles
maximum operating rate1800 cyc/h 60 °C
inrush power in VA95 VA 50 Hz cos phi 0.75 (at 20 °C)
95 VA 60 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA8.3 VA 50 Hz cos phi 0.3 (at 20 °C)
8.5 VA 60 Hz cos phi 0.3 (at 20 °C)
heat dissipation2…3 W for control circuit
minimum switching current5 mA for control circuit
minimum switching voltage17 V for control circuit
non-overlap time1.5 ms on energisation guaranteed between NC and NO contact
1.5 ms on de-energisation guaranteed between NC and NO contact
insulation resistance> 10 MOhm for control circuit
electrical durability1200000 cycles AC-3
350000 cycles AC-1
mounting supportDIN rail
Plate
connections - terminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 1…6 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end
Recommended tightening torqueControl circuit: 1.2 N.m
Power circuit: 1.5 N.m
Max tightening torqueControl circuit: 1.4 N.m
Power circuit: 1.7 N.m

Environment

standardsIEC 60947-1
IEC 60947-4-1
IEC 60947-5-1
product certificationsEAC
CE
IP degree of protectionIP2x conforming to IEC 60529
protective treatmentTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
pollution degree3
ambient air temperature for operation-5…55 °C
ambient air temperature for storage-60…80 °C
permissible ambient air temperature around the device-20…70 °C at Uc
operating altitude3000 m without derating
fire resistance850 °C conforming to IEC 60695-2-1
mechanical robustnessVibrations contactor open: 1.5 Gn, 5...300 Hz
Vibrations contactor closed: 3 Gn, 5...300 Hz
Shocks contactor closed: 10 Gn for 11 ms
Shocks contactor open: 6 Gn for 11 ms

Dimensions

Dimension LC1E25
Questions