Contactor LC1E200M5

  • Model: 004.005.184
Contactor LC1E200M5
Manufacturer: Schneider Electric
Barcode: 3606480323836
The E-line contactors LC1E200M5 200A 380V AC3 220V/50Hz offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.
Price by call

Main

range EasyPact
product name EasyPact TVS
product or component type Contactor
device short name LC1E
contactor application Resistive load
Motor control
utilisation category AC-1
AC-3
poles description 3P
power pole contact composition 3 NO
[Ue] rated operational voltage Power circuit: ≤ 690 V AC 50/60 Hz
[Ie] rated operational current 200 A (at < 55 °C) at ≤ 440 V AC AC-3 for power circuit
250 A (at < 40 °C) at ≤ 440 V AC AC-1 for power circuit
motor power kW 55 kW at 220...230 V AC 50/60 Hz
90 kW at 380...400 V
100 kW at 415 V
100 kW at 440 V
110 kW at 500 V
110 kW at 660...690 V
control circuit type AC at 50 Hz
[Uc] control circuit voltage 220 V AC 50 Hz
height 174 mm
width 168.5 mm
depth 181 mm
net weight 4.6 kg

Complementary

[Uimp] rated impulse withstand voltage 8 kV coil not connected to the power circuit conforming to IEC 60947
[Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1
overvoltage category III
Irms rated making capacity 2000 A at 440 V AC for power circuit conforming to IEC 60947-4-1
rated breaking capacity 1600 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 1500 A 40 °C - 10 s for power circuit
associated fuse rating 10 A gG at ≤ 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
315 A gG at ≤ 690 V coordination type 1 for power circuit
average impedance 0.33 mOhm - Ith 250 A 50 Hz for power circuit
power dissipation per pole 13 W AC-3
21 W AC-1
control circuit voltage limits Operational: 0.85...1.1 Uc at 50 Hz (at < 55 °C)
Drop-out: 0.35...0.55 Uc at 50 Hz (at < 55 °C)
operating time 20...35 ms on closing
7...15 ms on opening
mechanical durability 500000 cycles
maximum operating rate 1200 cyc/h 55 °C
inrush power in VA 805 VA 50 Hz cos phi 0.3 (at 20 °C)
970 VA 60 Hz cos phi 0.3 (at 20 °C)
hold-in power consumption in VA 55 VA 50 Hz cos phi 0.3 (at 20 °C)
66 VA 60 Hz cos phi 0.3 (at 20 °C)
heat dissipation 18…24 W for control circuit
minimum switching current 5 mA for control circuit
minimum switching voltage 17 V for control circuit
non-overlap time 1.5 ms on energisation guaranteed between NC and NO contact
1.5 ms on de-energisation guaranteed between NC and NO contact
insulation resistance > 10 MOhm for control circuit
electrical durability 500000 cycles AC-3
200000 cycles AC-1
mounting support Plate
connections - terminals Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: cable with lug - external diameter: 150 mm
Power circuit: bars 2 - busbar cross section: 3 x 25 mm
Recommended tightening torque Control circuit: 1.2 N.m
Power circuit: 18 N.m
Max tightening torque Control circuit: 1.4 N.m
Power circuit: 21 N.m

Environment

standards IEC 60947-1
IEC 60947-4-1
IEC 60947-5-1
product certifications EAC
IP degree of protection IP2x conforming to IEC 60529
protective treatment TH (pollution degree 3) conforming to IEC 60068
pollution degree 3
ambient air temperature for operation -5…55 °C
ambient air temperature for storage -60…80 °C
permissible ambient air temperature around the device -20…70 °C at Uc
operating altitude 3000 m without derating
fire resistance 850 °C conforming to IEC 60695-2-1
mechanical robustness Vibrations contactor open: 1.5 Gn, 5...300 Hz
Vibrations contactor closed: 3 Gn, 5...300 Hz
Shocks contactor open: 6 Gn for 11 ms
Shocks contactor closed: 7 Gn for 11 ms

Dimensions and internal circuit

Contactor LC1E200M5 dimensions   Contactor LC1E200M5 scheme
Questions