Contactor LC1E0601N5

  • Model: 004.005.127
Contactor LC1E0601N5
Manufacturer: Schneider Electric
Barcode: 3606480360862
The E-line contactors LC1E0601N5 1NC 6A 400V AC3 415V/50Hz offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.

Main

range EasyPact
product name EasyPact TVS
product or component type Contactor
device short name LC1E
contactor application Motor control
Resistive load
utilisation category AC-1
AC-3
poles description 3P
power pole contact composition 3 NO
[Ue] rated operational voltage Power circuit: ≤ 690 V AC 50/60 Hz
[Ie] rated operational current 6 A (at < 60 °C) at ≤ 440 V AC AC-3 for power circuit
20 A (at < 60 °C) at ≤ 440 V AC AC-1 for power circuit
motor power kW 1.1 kW at 220...230 V AC 50/60 Hz (AC-3)
2.2 kW at 380...400 V AC 50/60 Hz (AC-3)
2.2 kW at 415 V AC 50/60 Hz (AC-3)
2.2 kW at 440 V AC 50/60 Hz (AC-3)
3 kW at 500 V AC 50/60 Hz (AC-3)
3 kW at 660...690 V AC 50/60 Hz (AC-3)
control circuit type AC at 50 Hz
[Uc] control circuit voltage 415 V AC 50 Hz
height 74 mm
width 45 mm
depth 80 mm
net weight 0.3 kg
colour Grey (RAL 7011)

Complementary

auxiliary contact composition 1 NC
[Uimp] rated impulse withstand voltage 6 kV coil not connected to the power circuit conforming to IEC 60947
[Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1
overvoltage category III
Irms rated making capacity 60 A at 440 V AC for power circuit conforming to IEC 60947-4-1
rated breaking capacity 48 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 80 A 40 °C - 10 s for power circuit
45 A 40 °C - 60 s for power circuit
20 A 40 °C - 600 s for power circuit
associated fuse rating 10 A gG at ≤ 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
12 A gG at ≤ 690 V coordination type 1 for power circuit
average impedance 2.5 mOhm - Ith 20 A 50 Hz for power circuit
power dissipation per pole 0.09 W AC-3
1 W AC-1
control circuit voltage limits Operational: 0.85...1.1 Uc at 50 Hz (at < 55 °C)
Drop-out: 0.3...0.6 Uc at 50 Hz (at < 55 °C)
operating time 12...22 ms on closing
4...19 ms on opening
mechanical durability 10000000 cycles
maximum operating rate 1800 cyc/h 60 °C
inrush power in VA 95 VA 50 Hz cos phi 0.75 (at 20 °C)
95 VA 60 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA 8.5 VA 50 Hz cos phi 0.3 (at 20 °C)
8.5 VA 60 Hz cos phi 0.3 (at 20 °C)
heat dissipation 2…3 W for control circuit
minimum switching current 5 mA for control circuit
minimum switching voltage 17 V for control circuit
non-overlap time 1.5 ms on energisation guaranteed between NC and NO contact
1.5 ms on de-energisation guaranteed between NC and NO contact
insulation resistance > 10 MOhm for control circuit
electrical durability 1400000 cycles AC-3
150000 cycles AC-1
mounting support DIN rail
Plate
connections - terminals Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Recommended tightening torque Power circuit: 1.2 N.m
Control circuit: 1.2 N.m
Max tightening torque Power circuit: 1.4 N.m
Control circuit: 1.4 N.m

Environment

standards IEC 60947-4-1
IEC 60947-1
IEC 60947-5-1
product certifications EAC
IP degree of protection IP2x conforming to IEC 60529
protective treatment TH (pollution degree 3) conforming to IEC 60068
pollution degree 3
ambient air temperature for operation -5…55 °C
ambient air temperature for storage -60…80 °C
permissible ambient air temperature around the device -20…70 °C at Uc
operating altitude 3000 m without derating
fire resistance 850 °C conforming to IEC 60695-2-1
mechanical robustness Vibrations contactor open: 1.5 Gn, 5...300 Hz
Vibrations contactor closed: 3 Gn, 5...300 Hz
Shocks contactor open: 7 Gn for 11 ms
Shocks contactor closed: 10 Gn for 11 ms

Dimensions

Dimension LC1E06