Contactor CJX2-1801 18A 220V/AC3

  • Model: 004.003.605
Contactor CJX2-1801 18A 220V/AC3
CJX2-1801 AC contactor is suitable for using in the circuits up to the rated voltage 660V AC 50/60Hz, rated current 18A, for making, breaking, frequently starting and controlling the AC motor.
Combined with the auxiliary contact block, timer delay, machine-interlocking device, etc. it becomes the delay contactor, mechanical interlocking contactor, star-delta starter. With the thermal relay, it is combined into the electromagnetic starter.
The product conforms to IEC 60947-4-1 standard.
$8.36
 pcs

Main

[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Ui] rated insulation voltage
660 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV coil not connected to the power circuit conforming to IEC 60947
Utilisation categoryAC-3
AC-1
Poles description3
Auxiliary contact composition1 NC
[Ie] rated operational current32 A (at <60 °C) at <= 415 V AC AC-1 for power circuit
18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Motor power kW7.5 kW at 380...400 V AC 50/60 Hz (AC-3)
[Uc] control circuit voltage380...400Vac 50/60Hz
Control circuit voltage limitsOperational: 0.8...1.1 Uc at 50 Hz (at <55 °C)
Drop-out: 0.3...0.6 Uc at 50 Hz (at <55 °C)
Electrical durability, load AC-31 000 000 cycles
Mechanical durability
10 000 000 cycles
Mounting supportPlate
DIN rail

Dimensions and internal circuit

LC1-D1801 contactor size LC1-D1801 circuit

Auxiliaries and accessories for CJX2-D1801

background

 
 
background

 
 

Similar or replacement products CJX2-D1801

background
LC1-D1801-220VAC
 
 
background
LC1E1801M5
 
 
background
SQ0708-0012
 
 
Questions
WhatsAppTelegramViberVKemail