Double control input auxiliary A9C18308

  • Model: 004.016.108
Double control input auxiliary A9C18308
Manufacturer: Schneider Electric
Barcode: 3606480097928

Main

rangeActi 9
product or component typeDouble control input auxiliary
device short nameIACTc
[Uc] control circuit voltage230...240 V AC 50/60 Hz impulse 250 ms
230...240 V AC 50/60 Hz maintained
[Us] rated supply voltage220...240 V AC at 50/60 Hz

Complementary

maximum output current0.2 A holding
2 A inrush
hold-in power consumption in VA3 VA
mounting modeFixed, on the left of CT
mounting supportDIN rail
9 mm pitches2
height81 mm
width18 mm
depth60 mm
colourWhite
overvoltage categoryIII
[Uimp] rated impulse withstand voltage4 kV
[Ui] rated insulation voltage440 V
standardsIEC/EN 61095
connections - terminalsControl circuit: tunnel type terminals 2 cable(s) 2.5 mm² flexible
Control circuit: tunnel type terminals 2 cable(s) 1.5 mm² rigid
Control circuit: tunnel type terminals 1 cable(s) 1.5…2.5 mm² rigid
Control circuit: tunnel type terminals 1 cable(s) 1.5…2.5 mm² flexible with ferrule
Control circuit: yellow clips
wire stripping length9 mm
tightening torque0.8 N.m
range compatibilityActi9 iCT
market segmentSmall commercial
Residential
compatibility codeIACTc

Environment

IP degree of protectionIP20 conforming to IEC 60529
ambient air temperature for operation-5…50 °C
ambient air temperature for storage-40…70 °C
Questions