Motor Circuit Breaker GV3L50 for TeSys GV3L series

  • Model: 003.002.196
Motor Circuit Breaker GV3L50
Manufacturer: Schneider Electric
Barcode: 3389119405454

The TeSys GV3L50 circuit breaker is designed for the protection and control of 22kW electric motors (at 400...415Vac 50/60Hz).

The switch combines the following functions:
  • short circuit and overload protection
  • motor on / off control
  • contact position indication
Main characteristics:
  • electromagnetic release
  • rating of electromagnetic protection - 50A

Main

rangeTeSys
TeSys Deca
product nameTeSys GV3
TeSys Deca
product or component typeCircuit breaker
device short nameGV3L
device applicationMotor
poles description3P
network typeAC
utilisation categoryCategory A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
network frequency50/60 Hz
breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz
50 kA Icu at 440 V AC 50/60 Hz
12 kA Icu at 500 V AC 50/60 Hz
6 kA Icu at 690 V AC 50/60 Hz
50 kA Icu at 400/415 V AC 50/60 Hz
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz
100 % at 400/415 V AC 50/60 Hz
100 % at 440 V AC 50/60 Hz
50 % at 500 V AC 50/60 Hz
50 % at 690 V AC 50/60 Hz
trip unit technologyMagnetic
magnetic tripping current700 A

Complementary

fixing mode35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)
operating positionAny position
motor power kW22 kW at 400/415 V AC 50/60 Hz
30 kW at 500 V AC 50/60 Hz
45 kW at 690 V AC 50/60 Hz
control typeRotary knob
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
mechanical durability50000 cycles
electrical durability50000 cycles for AC-3 at 415 V
maximum operating rate25 cyc/h
connections - terminalsEverLink BTR screw connectors 1 cable(s) 1…35 mm² solid
EverLink BTR screw connectors 2 cable(s) 1…25 mm² solid
EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible without cable end
EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible without cable end
EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible with cable end
EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible with cable end
tightening torque5 N.m on EverLink BTR screw connectors for cable 25 mm²
8 N.m on EverLink BTR screw connectors for cable 35 mm²
mechanical robustnessShocks: 15 Gn for 11 ms closed conforming to IEC 60068-2-27
Shocks: 30 Gn for 11 ms opened conforming to IEC 60068-2-27
Vibrations: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
suitability for isolationYes conforming to IEC 60947-1
height132 mm
width55 mm
depth136 mm
product weight0.96 kg

Environment

standardsEN/IEC 60947-2
EN/IEC 60947-4-1
CSA C22.2 No 60947-4-1
UL 60947-4-1
product certificationsIECEE CB Scheme
UL
CSA
CCC
EAC
ABS
LROS (Lloyds register of shipping)
DNV-GL
BV
UKCA
protective treatmentTH
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK09
ambient air temperature for operation-20…60 °C
ambient air temperature for storage-40…80 °C
fire resistance960 °C conforming to IEC 60695-2-1
operating altitude0...3000 m

Dimension

Dimensions of the circuit breaker GV3L series
Electrical clearance X1=40mm for Ue≤ 500V
and X1=50mm for Ue≤ 690V

Scheme

Electrical scheme of the circuit breaker GV3L series

Range of TeSys GV3L series circuit breakers

Model Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 Magnetic protection rating Tripping current Id ± 20% Use in association with thermal overload relay (class 10 A)
400/415V 500V 690V
P Icu Ics P Icu Ics P Icu Ics
kW kA % kW kA % kW kA % A A
GV3L25 11 100 100 15 12 50 18.5 6 50 25 350 LRD 325
GV3L32 15 100 100 18.5 12 50 22 6 50 32 448 LRD 332
GV3L40 18.5 50 100 22 12 50 37 6 50 40 560 LRD 340
GV3L50 22 50 100 30 12 50 45 6 50 50 700 LRD 350
GV3L65 30 50 100 37 12 50 55 6 50 65 910 LRD 365
GV3L73 37 50 60 45 12 50 55 6 50 73 1120 LRD 380
GV3L80 45 50 60 45 12 50 55 6 50 80 1100 LRD 380

Auxiliaries and accessories for GV3L50

background
GV3APN01
 
 
background
GV3APN02
 
 
background
GV3APN04
 
 
background
GVAED101
 
 
background
GVAD0101
 
 
background
GVAN20
 
 
background
GVAN11
 
 
background
GVAE11
 
 
background
GVAU385
 
 
background
GVAS225
 
 
background
GVAD1010
 
 
Questions
WhatsAppTelegramViberVKemail