Circuit breaker EasyPact EZC100F3025 3P 25A 10kA/400V

  • Model: 003.002.414
Circuit breaker EasyPact EZC100F3025
Manufacturer: Schneider Electric
Barcode: 3303430300427
The EasyPact EZC100F3025 circuit breaker of the EZC100F series provides guaranteed disconnection in accordance with IEC 60947-2 and combines the following functions:
  • overload and short circuit protection
  • differential protection
Main characteristics:
  • thermal magnetic release
  • rated current - 25A
  • three-pole version
  • breaking capacity I cu at 400 ... 415V 10kA
$57.29
 pcs

Main characteristics

Range of productEasyPact
Product or component typeCircuit breaker
Device short nameEasypact EZC100F
Poles description3P
Protected poles description3t
Circuit typeDC
AC
Frequency50/60 Hz
[In] Rated current25 A (40 °C)
[Ui] Rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] Rated impulse witdstand voltage6 kV conforming to IEC 60947-2
[Ue] Rated operational voltage550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2
Breaking capacity codeF
Breaking capacity25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] Rated service breaking capacity12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolationconforming to IEC 60947-2
Utilisation categoryCategory A
Trip unit nameTM-D
Trip unit technologytdermal-magnetic
Protection typeShort-circuit protection
Overload protection
Pollution degree3 conforming to IEC 60664-1
3 conforming to IEC 947-1

Complementary characteristics

Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Mechanical durability8500 cycles
Electrical durabilityCategory A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Connection pitch25 mm
Local signallingPositive contact indication
Neutral protection settingWitdout protection
Eartd-leakage protectionWitdout
Height130 mm
Widtd75 mm
Deptd60 mm

Environment

StandardsJIS C8201-2-2
EN/IEC 60947-2
EN/IEC 60947-1
GB/T 14048.2
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-35…85 °C

Dimensions

EasyPact Schneider Electric 3-pole circuit breaker dimensions

Tripping curves

EasyPact Schneider Electric 25А circuit breaker tripping curves

EZC100 series circuit breakers model range

Number of polesRated current, ASchneider Electric catalogue number
Breaking capacity Icu at 220...240V18kA25kA
1

sketch of single pole switch EZC100
15EZC100N1015EZC100H1015
16EZC100N1016EZC100H1016
20EZC100N1020EZC100H1020
25EZC100N1025EZC100H1025
30EZC100N1030EZC100H1030
32EZC100N1032EZC100H1032
40EZC100N1040EZC100H1040
45EZC100N1045EZC100H1045
50EZC100N1050EZC100H1050
60EZC100N1060EZC100H1060
63EZC100N1063EZC100H1063
75EZC100N1075EZC100H1075
80EZC100N1080EZC100H1080
100EZC100N1100EZC100H1100
Breaking capacity Icu at 220...240V50kA
2

sketch of double pole switch EZC100
15EZC100H2015
16EZC100H2016
20EZC100H2020
25EZC100H2025
30EZC100H2030
32EZC100H2032
40EZC100H2040
45EZC100H2045
50EZC100H2050
60EZC100H2060
63EZC100H2063
75EZC100H2075
80EZC100H2080
100EZC100H2100
Breaking capacity Icu at 400...415V7.5kA10kA15kA30kA
3

sketch of three pole switch EZC100
15EZC100B3015EZC100F3015EZC100N3015EZC100H3015
16EZC100B3016EZC100F3016EZC100N3016EZC100H3016
20EZC100B3020EZC100F3020EZC100N3020EZC100H3020
25EZC100B3025EZC100F3025EZC100N3025EZC100H3025
30EZC100B3030EZC100F3030EZC100N3030EZC100H3030
32EZC100B3032EZC100F3032EZC100N3032EZC100H3032
40EZC100B3040EZC100F3040EZC100N3040EZC100H3040
45EZC100B3045EZC100F3045EZC100N3045EZC100H3045
50EZC100B3050EZC100F3050EZC100N3050EZC100H3050
60EZC100B3060EZC100F3060EZC100N3060EZC100H3060
63EZC100F3063EZC100N3063EZC100H3063
75EZC100F3075EZC100N3075EZC100H3075
80EZC100F3080EZC100N3080EZC100H3080
100EZC100F3100EZC100N3100EZC100H3100
Breaking capacity Icu at 400...415V15kA30kA
4

sketch of four pole switch EZC100
15EZC100N4015EZC100H4015
16EZC100N4016EZC100H4016
20EZC100N4020EZC100H4020
25EZC100N4025EZC100H4025
30EZC100N4030EZC100H4030
32EZC100N4032EZC100H4032
40EZC100N4040EZC100H4040
45EZC100N4045EZC100H4045
50EZC100N4050EZC100H4050
60EZC100N4060EZC100H4060
63EZC100N4063EZC100H4063
75EZC100N4075EZC100H4075
80EZC100N4080EZC100H4080
100EZC100N4100EZC100H4100

Auxiliaries and accessories for EZC100F3025

background
EZAROTDSRY
 
 
background
EZAROTDS
 
 
background
EZAROTE
 
 
background
EZAROTERY
 
 
background
EZADINR
 
 
background
EZAFASB2
 
 
background
EZAFSHB3
 
 
background
EZALOCK
 
 
background
EZALUG0502
 
 
background
EZALUG0503
 
 
background
EZALUG1002
 
 
background
EZAPCON1H
 
 
background
EZAPCON1L
 
 
background
EZAPLUG3H
 
 
background
EZAUX01
 
 
background
EZAUX10
 
 
background
EZAUX11
 
 
background
EZAUVR024DC
 
 
background
EZAUVR048DC
 
 
background
EZAUVR110AC
 
 
background
EZAUVR200AC
 
 
background
EZAUVR380AC
 
 
background
EZASHT024DC
 
 
background
EZASHT048DC
 
 
background
EZASHT100AC
 
 
background
EZASHT200AC
 
 
background
EZASHT380AC
 
 
background
EZASPDR3P
 
 
background
EZATSHD3P
 
 
background
EZAPLUG3L
 
 
background
EZALUG1003
 
 
Questions
WhatsAppTelegramViberVKemail