Circuit breaker Easy9 EZ9F34210 2P 10A C 4.5kA 230V AC

  • Model:
    003.002.321
  • Copy
Circuit breaker Easy9 EZ9F34210
Manufacturer: Schneider Electric
Barcode: 3606480586927
Easy9 EZ9F34210 circuit breaker is designed to perform the following functions:
  • protection of circuits against short-circuit currents
  • overload current protection
Fault-tripping indication on the front panel by the position of the handle (O-I engraved).

Main

rangeEasy9
device applicationDistribution
product or component typeMiniature circuit-breaker
device short nameEasy9 MCB
Poles2P
number of protected poles2
[In] rated current10 A
network typeAC
trip unit technologyThermal-magnetic
curve codeC
breaking capacity4500 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
4500 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
suitability for isolationYes conforming to IEC 60898-1

Complementary

network frequency50 Hz
[Ue] rated operational voltage400 V AC 50 Hz
magnetic tripping limit5...10 x In
[Ics] rated service breaking capacity4.5 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60898-1
[Uimp] rated impulse withstand voltage4 kV conforming to IEC 60898-1
contact position indicatorYes
control typeToggle
local signallingWithout
mounting modeClip-on
mounting supportDIN rail
9 mm pitches4
height81 mm
width36 mm
depth66.5 mm
colourGrey (RAL 7035)
mechanical durability10000 cycles
electrical durability4000 cycles
connections - terminalsTunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible
tightening torque2 N.m top or bottom

Environment

standardsIEC 60898-1
product certificationsGOST-R
IP degree of protectionIP20 conforming to IEC 60529
pollution degree2
tropicalisation2
relative humidity95 % at -25…60 °C
ambient air temperature for operation-25…60 °C
ambient air temperature for storage-40…85 °C

Dimensions

Circuit breaker dimensions

Model range of Easy9 series circuit breakers

Number of poles Rated current, A Schneider Electric catalogue number
Curve B Curve C
1

Type designation 1P
6 EZ9F14106 EZ9F34106
10 EZ9F14110 EZ9F34110
16 EZ9F14116 EZ9F34116
20 EZ9F14120 EZ9F14120
25 EZ9F14125 EZ9F34125
32 EZ9F14132 EZ9F34132
40 EZ9F14140 EZ9F34140
50 EZ9F14150 EZ9F34150
63 EZ9F14163 EZ9F34163
2

Type designation 2P
6 EZ9F14206 EZ9F34206
10 EZ9F14210 EZ9F34210
16 EZ9F14216 EZ9F34216
20 EZ9F14220 EZ9F34220
25 EZ9F14225 EZ9F34225
32 EZ9F14232 EZ9F34232
40 EZ9F14240 EZ9F34240
50 EZ9F14250 EZ9F34250
63 EZ9F14263 EZ9F34263
3

Type designation 3P
6 EZ9F14306 EZ9F34306
10 EZ9F14310 EZ9F34310
16 EZ9F14316 EZ9F34316
20 EZ9F14320 EZ9F34320
25 EZ9F14325 EZ9F34325
32 EZ9F14332 EZ9F34332
40 EZ9F14340 EZ9F34340
50 EZ9F14350 EZ9F34350
63 EZ9F14363 EZ9F34363
4

Type designation 4P
6 EZ9F14406 EZ9F34406
10 EZ9F14410 EZ9F34410
16 EZ9F14416 EZ9F34416
20 EZ9F14420 EZ9F34420
25 EZ9F14425 EZ9F34425
32 EZ9F14432 EZ9F34432
40 EZ9F14440 EZ9F34440
50 EZ9F14450 EZ9F34450
63 EZ9F14463 EZ9F34463

Dimensions

Circuit breakers dimensions