Circuit breaker C120H A9N18412 2P 63A B

  • Model: 003.001.052
Circuit breaker C120H A9N18412
Manufacturer: Schneider Electric
Barcode: 3606480379833
The C120H A9N18412 circuit breaker meets the requirements of the standards EN 60947-2, EN 60898-1 and combines the following functions:
  • protection of circuits against short-circuit currents
  • overload current protection
  • fault signaling and emergency shutdown by means of optional accessories

Main

range of productC120
rangeActi 9
product nameC120
product or component typeMiniature circuit-breaker
device short nameC120H
device applicationDistribution
poles description2P
number of protected poles2
neutral positionLeft
[In] rated current63 A at 30 °C
network typeAC
trip unit technologyThermal-magnetic
curve codeB
breaking capacity15000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at ≤ 250 V DC conforming to EN/IEC 60947-2
15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
suitability for isolationYes conforming to IEC 60947-2

Complementary

network frequency50/60 Hz
[Ue] rated operational voltage380...415 V AC 50/60 Hz
220...240 V AC 50/60 Hz
440 V AC 50/60 Hz
≤ 250 V DC
230...400 V AC 50/60 Hz
magnetic tripping limit3...5 x In
[Ics] rated service breaking capacity7500 A 50 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz
5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 - ≤ 250 V DC
limitation class3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
contact position indicatorYes
control typeToggle
local signallingON/OFF indication
mounting modeClip-on
mounting support35 mm symmetrical DIN rail
comb busbar and distribution block compatibilityYES
9 mm pitches6
height81 mm
width54 mm
depth73 mm
net weight0.41 kg
colourWhite
mechanical durability20000 cycles
electrical durability10000 cycles conforming to IEC 60947-2
connections - terminalsTunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible
wire stripping length15 mm
tightening torque3.5 N.m
earth-leakage protectionSeparate block

Environment

standardsEN/IEC 60947-2
EN/IEC 60898-1
product certificationsEAC
IP degree of protectionIP20 conforming to IEC 60529
pollution degree3 conforming to IEC 60947-2
overvoltage categoryIV
tropicalisation2 conforming to IEC 60068-1
relative humidity95 % at 55 °C
operating altitude2000 m
ambient air temperature for operation-30…60 °C
ambient air temperature for storage-40…70 °C

Nomenclature of circuit breakers C120H

Dimensions circuit breaker C120H

Dimensions circuit breaker C120H

Trip curves

Curve В Curve C Curve D
Questions
WhatsAppTelegramViberVKemail