EZAUVR048DC Undervoltage release UVR for EZC100

  • Model: 003.002.134
EZAUVR048DC Undervoltage release UVR
Manufacturer: Schneider Electric
Barcode: 3303430301745
Undervoltage release UVR EZAUVR048DC use for EZC100 series.
Control circuit voltage - 48 V DC.

Under Voltage Release (UVR) this release trips the circuit breaker when the control voltage drops below a tripping threshold.

Tripping threshold between 0.35 and 0.7 times the rated voltage.

Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltage.

Operation

When the circuit breaker has been tripped by an UVR release, it must be reset locally:

  • UVR tripping takes priority over manual closing.
  • in the presence of a standing trip order, closing of the contacts, even temporary, is not possible.

Circuit breaker tripping by an UVR release meets the requirements of standard IEC 60947-2.

Specification

Range of productEasyPact
Device short nameMN
Product or component type
Voltage release
Device applicationControl
Range compatibility
EasyPact EZC
Voltage release type
Undervoltage release
[Uc] Control circuit voltage
48 V DC
Threshold tripping voltage0.35...0.7 Un opening
0.85 Un closing
Response time
50 ms

Nomenclature undervoltage release UVR

ModelVoltage, V
EZAUVR110AC110-130 VAC
EZAUVR200AC200-240 VAC
EZAUVR380AC380-415 VAC
EZAUVR024DC24 VDC
EZAUVR048DC48 VDC
Questions
WhatsAppTelegramViberVKemail