Under Voltage Release (UVR) this release trips the circuit breaker when the control voltage drops below a tripping threshold.
Tripping threshold between 0.35 and 0.7 times the rated voltage.
Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltage.
Operation
When the circuit breaker has been tripped by an UVR release, it must be reset locally:
Circuit breaker tripping by an UVR release meets the requirements of standard IEC 60947-2.