Thermostat KTS 01156

  • Model: 010.007.023
Thermostat KTS 01156
Manufacturer: Essima
Mechanical adjusting thermostat KTS 01156 is designed to close electrical circuit when temperature is set in the range -15...+45°C. Thermostat doesn't consume power.
Operation of the thermostat is based on the principle of bimetallic plate deformation.
$3.19
 pcs

Technical data

Rated current10(2)A 250V AC
Temperature setting range-15°С ... +45°С
Operating/Storage temperature-20°С ... +80°С
Tolerance±4°C
Hysteresis7°C

Installation and adjustment instructions

The thermoregulator controls temperature in an electric cabinet. It must be mounted in an upper part of the enclosure at a maximum distance from a heating device or other heat sources. It is designed to be mounted on a standard 35mm DIN rail by snap-in mounting.  Ventilation slots of the thermostat must not be closed.
Thermostat adjustment should be made with regard to its tolerance. For example, a maximum allowed temperature in an electric cabinet is +45°C. The maximum tolerance of the thermostat is +4°C, so it is necessary to set 41°C (45°C-4°C) on a thermostat knob.

Thermostats model range

Temperature adjusting rangeNO contactNC contact
0...+60°СNO contact  NO contactKTS 01141NC contact  NC contactKTO 01140
-10...+50°СNO contact  NO contactKTS 01143NC contact  NC contactKTO 01142
-15...+45°CNO contact  NO contactKTS 01156 NC contact  NC contactKTO 01157
+20...+80°СNO contact  NO contactKTS 01158NC contact  NC contactKTO 01159

Wiring Diagram

thermoregulator scheme KTS 01156

Dimensions

thermostat dimensions KTS 1156

Example of connection

example of thermostat connection KTS 01156